Additional Functions and Connections
16
Fuses
Label Capacity Description
Mains 1.6 A, slow Power supply line 230V AC
24 V 1 A, slow Power output 24V DC
Terminals 9 + 10
Warning light 1 A, slow Warning light output 24V DC
Terminals 11 + 12
Admissible cable diameters for all terminals: 1 mm² - 2.5 mm²
potential-free relay contact
Terminal Description Function
25 + 26 Special funct. Connection for electric lock, etc.
max. 8A, 24V DC at ohmic load
Connecting Safety Devices
For operation with automatic close mode, comply with EN 12453
(e.g. installation of light barrier).
Factory settings: Bridge between terminals 17 + 18.
Terminal Label Function
17 + 18 Sicherh. Connection for safety devices, e.g.
- Light barrier
- Contact strip
If the connected safety device is not
triggered, the contact must be closed.
If the contact is not used, mount a bridge
between the terminals (factory settings).
Use contact only for potential-free normally closed contacts.
External voltage may damage the control system.
Connect keys
Terminal Label Function
13 + 14 Impuls Connection for pulse key used to operate
one or both gate wings.
15 + 16 Gehtur Connection for pulse key used to operate
one gate wing.
Use contact only for potential-free normally closed contacts.
External voltage may damage the control system.
A 2-contact key is only required for double-wing gates, and if the pedestrian
gate function is to be used.
In single-wing gates, the pulse and the pedestrian gate key are assigned
identical functions.
Connection Key 1 Contact:
single-wing gate system Key to terminals 13 + 14 or 15 + 16
double-wing gate system Key to terminals 13 + 14
Connection Key 2 Contact
Pedestrian gate terminals 15 + 16
Both wings terminals 13 + 14
Connecting warning lamp
Available as optional accessories.
For function settings, see DIL switches 4 + 5
Terminal Label Function
11 + 12 24V Warning lamp Connection for 24 V warning lamp , fused
with 1A at max. 20W.
Rectified, not stabilised transformer voltage, fluctuating
between 22V and 27V at full load.