INSTRUCTION MANUAL OF THE SIEMENS CLIMATIX 2 CONTROL EQUIPMENT
-
55
-
simultaneously. When the boiler switches to the mode “Reduce” or when the boiler turns off, the
flue gas outlet turns off after its overrun time.
The default value is Ignition. The instructions for changing this parameter can be found in chapter
4.
The Overrun time of flue gas outlet parameter determines the delay time of putting the flue gas
outlet out of operation compared to the ignition aggregate (or the combustion air fan).
The parameter setting is ranging from 0 – 300 sec; the default value is 20 sec.
The instructions for changing this parameter can be found in chapter 4.
7.7. PARAMETERS FOR BACKFIRE
In order to minimize the risk of backfire of the fuel in the storage tank, the control equipment
communicates with the backfire sensor which is installed in the feeding mechanism. If this sensor
monitors the unacceptable increase in the feeder temperature (c. 100°C), the transport of fuel into
the burner accelerates (as defined by the parameters Feeding time and Delay time described in
this chapter) for the time that is defined by the parameter Protection time. After this time passes,
during the Intervention period, the backfire control is not taken into consideration (this period is
intended for cooling the feeding mechanism) and the boiler operates in the normal mode.
The Feeding time parameter determines how long the screw feeder is in operation during
activation of the backfire sensor.
The parameter setting is ranging from 2 – 10 s; the default value is 5 s.
The instructions for changing this parameter can be found in chapter 4.
The Delay time parameter determines how long the screw feeder is out of operation during
activation of the backfire sensor.
The parameter setting is ranging from 5 – 60 s; the default value is 20 s.
The instructions for changing this parameter can be found in chapter 4.
The Protection time parameter determines how long the accelerated fuel feeding is active after
activation of the backfire sensor.
The parameter setting is ranging from 1 – 30 min; the default value is 5 min.
The instructions for changing this parameter can be found in chapter 4.
The Intervention period parameter determines how long it takes before the activation of the
backfire sensor is re-evaluated. Then, the transport of fuel into the burner can be accelerated
again.
The parameter setting is ranging from 10 – 120 min; the default value is 60 min.
The instructions for changing this parameter can be found in chapter 4.
7.8. SUBSTITUTE OPERATION
This function is activated only if the function Cascade in the Configuration (chap. 7.1.) is turned
off.
The selection Including boiler OFF - YES enables to control the appliances even if the boiler is
turned off. It is assumed that a substitute unit is available.
55


Need help? Post your question in this forum.

Forumrules
1

Forum

siemens-climatix-2

Reset search

  • salve
    chiedo se è possibile fare un by pass per far partire il sistema di condizionamento a causa dell'oscuramento :del controllore POL/STD
    grazie
    Submitted on 11-3-2022 at 12:44

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens Climatix 2 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens Climatix 2 in the language / languages: English as an attachment in your email.

The manual is 1,35 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info