INSTRUCTION MANUAL OF THE SIEMENS CLIMATIX 2 CONTROL EQUIPMENT
-
53
-
Outside temperature Pump mode
< -4 °C The pump is permanently ON.
-4 to 1.5 °C The pump turns on every 6 h for 10 min.
> 1.5 °C The pump is permanently OFF.
The default value is OFF. The instructions for changing this parameter can be found in chapter 4.
7.5. IGNITION
This program enables to control and optimize the process of automatic ignition of the burner by
using an ignition aggregate (a heat gun or an incandescent electrode) when the boiler is put into
operation.
The ignition process is considered successful if at least one of the conditions set in the Differential
flue gas - water or Boost flue gas temperature parameters is met.
After clicking on the line Ignition it is possible to enter the menu concerning the setting of ignition
parameters:
The First feeding parameter determines how long Feeder 1 and Feeder 2 are in operation after
the boiler is turned on (or after automatic emptying) and before the mode Ignition” is activated.
The length of this period depends on the feeder construction and it must be set in such a way that
the fuel level reaches approximately the top surface of the grate when the time set in First feeding
passes. If it is necessary to turn off Feeder 1 or Feeder 2 prematurely, during the First feeding,
button “A” must be pressed (see chap. 2.), to enter the file Quick access (see chap. 6.15.).
This parameter can be found only in the configuration Ignition – YES, Emptying - YES.
The parameter setting is ranging from 10 – 600 s; the default value is 260 s.
The instructions for changing this parameter can be found in chapter 4.
The Second feeding parameter determines how long Feeder 1 and Feeder 2 are in operation
between the cycles of the mode “Ignition”.
The parameter setting is ranging from 5 – 50 s; the default value is 10 s.
The instructions for changing this parameter can be found in chapter 4.
The Ignition time parameter determines how long the ignition aggregate can be in continuous
operation during the process of “Ignition”.
The parameter setting is ranging from 1 – 15 min; the default value is 4.0 min.
The instructions for changing this parameter can be found in chapter 4.
The Differential flue gas - water parameter determines the minimum difference that must be
between the flue gas temperature and the boiler temperature so that the ignition process can be
considered successful.
The parameter setting is ranging from -5 to 30 K; the default value is 6 K.
The instructions for changing this parameter can be found in chapter 4.
The Flue gas differential parameter is related to the Differential flue gas - water parameter. It
determines when the ignition turns off again according to the difference between the flue gas
temperature and the water temperature.
The parameter setting is ranging from 1 – 30 K; the default value is 1 K.
The instructions for changing this parameter can be found in chapter 4.
53


Need help? Post your question in this forum.

Forumrules
1

Forum

siemens-climatix-2

Reset search

  • salve
    chiedo se è possibile fare un by pass per far partire il sistema di condizionamento a causa dell'oscuramento :del controllore POL/STD
    grazie
    Submitted on 11-3-2022 at 12:44

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens Climatix 2 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens Climatix 2 in the language / languages: English as an attachment in your email.

The manual is 1,35 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info