INSTRUCTION MANUAL OF THE SIEMENS CLIMATIX 2 CONTROL EQUIPMENT
-
52
-
WARNING!!! After the functionality check, it is necessary to switch all the aggregates to the mode
Auto again. The indicators on buttons "A" and "B" - see chap. 2 - stop blinking.
7.4. BOILER PUMP
The line Boiler pump is used to set all the parameters that are necessary for correct operation of
the pump of the primary circuit.
The parameter Switch ON temperature determines the temperature at which the pump of the
primary circuit is turned on if this pump is controlled by the control equipment of the boiler.
The parameter setting is ranging from 40 – 60 °C; the default value is 45 °C.
The instructions for changing this parameter can be found in chapter 4.
When water in the boiler is cooling, the pump of the primary circuit is turned off according to the
hysteresis set in the Differential OFF parameter and after expiry of a period set in the Pump
overrun time parameter.
The setting of the parameter Differential OFF is ranging from 1 to 10 °C; the default value is 5 °C.
The instructions for changing this parameter can be found in chapter 4.
The setting of the parameter Pump overrun time is ranging from 0 – 30 min; the default value is 2
min.
The instructions for changing this parameter can be found in chapter 4.
Example:
The values set in the control equipment are:
- Switch ON temperature 45 °C
- Differential OFF 5 °C
- Pump overrun time 2 min
If the boiler is put into operation, the temperature of water in the boiler starts to rise. If it
reaches the value of 45 °C, the pump of the primary circuit turns on. If the temperature of
water in the boiler starts to fall, for any reason, and if it reaches the value of 40 °C (45-5=40)
and this value does not change for 2 min, the pump turns off.
After passing the time set in the Pump overrun time parameter, the pump also turns off if the
boiler switches to the mode “External reduce” - see chap. 6.2. - or if the room thermostat of the
external input disconnects. If they connect again, the pump automatically turns on.
If the temperature of water in the boiler rises above 85 °C, the boiler pump is in continuous
operation, regardless of the operating mode of the boiler. It turns off if the temperature falls below
85 °C and the overrun time is 2 min.
The selection Frost protection (OFF/ON) defines whether pump of the primary circuit is in the
mode “frost protection” or not. If ON is selected, the pump of the primary circuit is turned on
according to the actual value of the outside temperature B9, even if no demand on heating is
received.
52


Need help? Post your question in this forum.

Forumrules
1

Forum

siemens-climatix-2

Reset search

  • salve
    chiedo se è possibile fare un by pass per far partire il sistema di condizionamento a causa dell'oscuramento :del controllore POL/STD
    grazie
    Submitted on 11-3-2022 at 12:44

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens Climatix 2 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens Climatix 2 in the language / languages: English as an attachment in your email.

The manual is 1,35 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info