INSTRUCTION MANUAL OF THE SIEMENS CLIMATIX 2 CONTROL EQUIPMENT
-
50
-
The Release integral parameter determines how fast the boiler turns on after its releasing from
temperature (B10).
The parameter setting is ranging from 0 – 500; the default value is 10.
The instructions for changing this parameter can be found in chapter 4.
The Run Up time parameter determines how much time passes from the moment when the
demand of the boiler on switching on is received to the moment when the boiler starts to transmit
heat into the system.
The parameter setting is ranging from 0 – 90 min; the default value is 4 min.
The instructions for changing this parameter can be found in chapter 4.
The Reverse integral parameter determines how fast the boiler turns off after its reduce from
temperature (B10).
The parameter setting is ranging from 0 – 500; the default value is 10.
The instructions for changing this parameter can be found in chapter 4.
The Restart after blackout parameter determines the speed (expressed in %/s) of the gradual
releasing of the cascade power (2 boilers cascade power from 0 to 200%, 4 boilers cascade
power from 0 to 400%).
The parameter setting is ranging from 0 – 20; the default value is 0.5.
The instructions for changing this parameter can be found in chapter 4.
The Boost lead boiler parameter determines the value to which the required temperature of the
lead boiler in the cascade can rise from the value of the required temperature of the sensor B10.
The parameter setting is ranging from 5 – 20 K; the default value is 10 K.
The instructions for changing this parameter can be found in chapter 4.
The Boost lag boiler parameter determines the value to which the required temperature of other
boilers in the cascade can rise from the value of the required temperature of the sensor B10.
The parameter setting is ranging from 5 – 20 K; the default value is 15 K.
The instructions for changing this parameter can be found in chapter 4.
The selection Boiler sequence (Auto/Boiler 1/ Boiler 2/ Boiler 3/ Boiler 4) determines which of the
boilers will be the first one in the cascade. The selection Auto is based on the operating hours of
the boilers; the defined boiler will be the first one in the cascade regardless of the operating hours.
The instructions for changing this parameter can be found in chapter 4.
The Sequencing period parameter determines how much time passes before the automatic
sequencing of boilers in the cascade changes.
The parameter setting is ranging from 0 – 1000 h; the default value is 500 h.
The instructions for changing this parameter can be found in chapter 4.
The Minimum ON time of a boiler parameter determines how long the boiler is in operation after
being turned on.
The parameter setting is ranging from 0 – 30 min; the default value is 10 min.
The instructions for changing this parameter can be found in chapter 4.
The Minimum OFF time of a boiler parameter determines how long the boiler is out of operation
after being turned off.
The parameter setting is ranging from 0 – 30 min; the default value is 5 min.
The instructions for changing this parameter can be found in chapter 4.
50


Need help? Post your question in this forum.

Forumrules
1

Forum

siemens-climatix-2

Reset search

  • salve
    chiedo se è possibile fare un by pass per far partire il sistema di condizionamento a causa dell'oscuramento :del controllore POL/STD
    grazie
    Submitted on 11-3-2022 at 12:44

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens Climatix 2 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens Climatix 2 in the language / languages: English as an attachment in your email.

The manual is 1,35 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info