6.2. REDUCE
Reduce is the economical boiler operation when only the minimal amount of fuel is fed into the
furnace and the cycles are Feeding time during reduce and Delay time during reduce. This
prevents the boiler from dying out and prevents the fuel in the storage tank from backfire. The fan
operation is reduced only at the time when the feeder is on.
There are two ways to put the boiler into reduce operation:
A) Reduce from temperature - if the instantaneous value of Boiler temperature exceeds the
Actual required temperature by the value of the temperature hysteresis set
in Hysteresis OFF boiler (see chap. 5.10.).
B) External reduce - if the room thermostat or the external input is undone. This does not happen if
the function Ignition YES, Emptying YES is activated in the configuration
(see chap. 7.1.).
The parameter setting of Feeding time during reduce is ranging from 2 15 s; the default value
is 5 s.
The instructions for changing this parameter can be found in chapter 4.
The parameter setting of Delay time during reduce is ranging from 1 60 min; the default value
is 5 min, which is the recommended value if wood pellets are used. If brown coal is used, it is
recommended to change this value to 30 min.
The instructions for changing this parameter can be found in chapter 4.
The fan speed at the feeding time during reduce is set in Fan power.
The parameter setting of Fan power is ranging from 20 – 100 %; the default value is 40 %.
The instructions for changing this parameter can be found in chapter 4.
Turning off of the fan after the feeding time during reduce is delayed and it is set in Fan overrun
time.
The parameter setting of Fan overrun time is ranging from 0 300 sec; the default value is 30
sec.
The instructions for changing this parameter can be found in chapter 4.
6.2.1. FLAME CONTROL
This function controls the furnace (flame) according to the difference between B8 Flue gas
temperature and B2 Boiler temperature. The furnace is controlled primarily during these
operation states of the boiler:
reduce during configuration Ignition – YES
reduce during configuration Ignition – NO
operation during configuration Ignition – NO
After entering the service password (see chap. 5.24.) it is possible to set these parameters:
The Minimum flue gas temperature means that if the temperature is lower than this limit, the
boiler is put out of operation and the error mode “Low flue gas temperature B8” is activated.
30


Need help? Post your question in this forum.

Forumrules
1

Forum

siemens-climatix-2

Reset search

  • salve
    chiedo se è possibile fare un by pass per far partire il sistema di condizionamento a causa dell'oscuramento :del controllore POL/STD
    grazie
    Submitted on 11-3-2022 at 12:44

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens Climatix 2 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens Climatix 2 in the language / languages: English as an attachment in your email.

The manual is 1,35 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info