INSTRUCTION MANUAL OF THE SIEMENS CLIMATIX 2 CONTROL EQUIPMENT
-
31
-
The parameter setting is ranging from 0 – 190°C; the default value is 35°C.
The instructions for changing this parameter can be found in chapter 4.
The Differential B2 B8 reduce parameter determines the maximal difference (in Kelvin) between
the boiler temperature B2 during reduce and the flue gas temperature B8. The setting 25 K means
that the difference between the flue gas temperature during reduce and the boiler temperature can
be 25 K at the maximum, otherwise the error mode “Loss of flame – reduce“ is activated.
The parameter setting is ranging from -30 to 60 K; the default value is 25 K.
The instructions for changing this parameter can be found in chapter 4.
The Error delay number cycles parameter determines how many cycles of feeding during reduce
must pass before the error mode “Loss of flame reduce” is activated. It is determined according
to the difference between the boiler temperature B2 and the flue gas temperature B8 (see the
Differential B2 B8 reduce parameter).
The parameter setting is ranging from 0 – 20 cycles; the default value is 3 cycles.
The instructions for changing this parameter can be found in chapter 4.
The Delay time of ignition after reduce parameter determines how long the temperature
conditions for ignition are ignored after the switchover from reduce to operation and determines the
time which is necessary for the boiler to begin to burn. If this time passes and the conditions for the
boiler operation are not met, the automatic ignition is activated.
This parameter can be found only in the configuration Ignition – YES.
The parameter setting is ranging from 0 - 600 s; the default value is 280 s.
The instructions for changing this parameter can be found in chapter 4.
The Differential B8 B2 operation parameter determines the minimal difference (in Kelvin)
between the flue gas temperature B8 and the boiler temperature B2 in operation. The setting 1
K means that the flue gas temperature B8 in operation must be by 1 K higher than the boiler
temperature, otherwise the error mode “Loss of flame - operation” is activated.
This parameter can be found only in the configuration Ignition – NO.
The parameter setting is ranging from -10 to 30 K; the default value is 1 K.
The instructions for changing this parameter can be found in chapter 4.
The Hysteresis differential B8 B2 operation parameter determines when the acceptable
operation state of the boiler is re-evaluated.
In order to deactivate the error mode “Loss of flame – operation“, the flue gas temperature must be
higher than Differential B8 B2 operation + Hysteresis differential B8 B2 operation.
This parameter can be found only in the configuration Ignition – NO.
The parameter setting is ranging from 1 - 30 K; the default value is 1 K.
The instructions for changing this parameter can be found in chapter 4.
The Delay of loss of flame parameter determines how long the flue gas temperature B8 can be
beyond permitted limits compared to the boiler temperature B2, without activation of the error
mode “Loss of flame – operation“.
This parameter can be found only in the configuration Ignition – NO.
The parameter setting is ranging from 0 – 800 s; the default value is 400 s.
The instructions for changing this parameter can be found in chapter 4.
If for any reasons (e.g. a lack of fuel in the storage tank) the boiler temperature falls below the limit
Low boiler temperature for the duration of Delay, the boiler is put out of operation and reports a
failure. During the first 30 min. of ignition this condition does not apply.
31


Need help? Post your question in this forum.

Forumrules
1

Forum

siemens-climatix-2

Reset search

  • salve
    chiedo se è possibile fare un by pass per far partire il sistema di condizionamento a causa dell'oscuramento :del controllore POL/STD
    grazie
    Submitted on 11-3-2022 at 12:44

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens Climatix 2 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens Climatix 2 in the language / languages: English as an attachment in your email.

The manual is 1,35 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info