INSTRUCTION MANUAL OF THE SIEMENS CLIMATIX 2 CONTROL EQUIPMENT
-
32
-
This parameter can be found only in the configuration Ignition – NO.
The parameter setting of Low boiler temperature is ranging from 10 55 °C; the default value is
30 °C.
The instructions for changing this parameter can be found in chapter 4.
The parameter setting of Delay is ranging from 0 – 120 min; the default value is 60 min.
The instructions for changing this parameter can be found in chapter 4.
6.3. DEASHER
If any additional attachment of the boiler is used (e.g. a deasher, a rotary grate, an additive feeder,
etc.), which is put into operation at regular intervals, it is possible to control this additional
attachment by the binary output DEASHER.
The Number of feeding parameter determines how often the additional attachment is put into
operation. The Time of deashing parameter determines how long the additional attachment is in
operation.
The values of Actual number of feeding are monitored, i.e. how many times the fuel feeder turns
on. If the number reaches the value set in the Number of feeding parameter, the additional
attachment is put back into operation for the duration of Time of deashing. Actual number of
feeding is at the same time automatically zeroed and the counting starts again.
The parameter setting of Number of feeding is ranging from 1 – 400x; the default value is 40x.
The instructions for changing this parameter can be found in chapter 4.
The parameter setting of Time of deashing is ranging from 5 – 120 s; the default value is 15 s.
The instructions for changing this parameter can be found in chapter 4.
6.4. HEATING CIRCUIT 1
All parameters related to the heating circuit 1 control can be set here.
6.4.1. HEATING CIRCUIT 1
The Heating circuit 1 parameter determines whether the mode of the heating circuit 1 control will
be:
Auto – HC1 is controlled according to the TSP HC1
Frost protection – the constant internal temperature in the reference room is held as set in
Frost protection
Reduce – the constant internal temperature in the reference room is held as set in Reduce
Comfort – the constant internal temperature in the reference room is held as set in
Comfort
The default value is Auto.
The instructions for changing this parameter can be found in chapter 4.
32


Need help? Post your question in this forum.

Forumrules
1

Forum

siemens-climatix-2

Reset search

  • salve
    chiedo se è possibile fare un by pass per far partire il sistema di condizionamento a causa dell'oscuramento :del controllore POL/STD
    grazie
    Submitted on 11-3-2022 at 12:44

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens Climatix 2 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens Climatix 2 in the language / languages: English as an attachment in your email.

The manual is 1,35 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info