Installation Indications, functions and options MessagesCommissioningOperation and function
Collector minimum limitation
OCN / OCN1 / OCN2
Collector minimum limitation option
Adjustment range: OFF / ON
Factory setting: OFF
CMN / CMN1 / CMN2
Minimum collector temperature
Adjustment range:
10.0 … 90.0 °C [50.0 … 190.0 °F]
Factory setting: 10.0 °C [50.0 °F]
If the collector minimum limitation option is activated, the pump (R1 / R2) will only
be switched on, if the adjustable collector minimum temperature is exceeded. The
minimum temperature prevents the pump from being switched on too often at low
collector temperatures. A hysteresis of 5 K [10 °Ra] is set for this function. If the
collector minimum limitation is active, is displayed (ashing).
Note
If OSTC or OCF is active, the collector minimum limitation will be over-
ridden. In that case, the collector temperature may fall below CMN.
Antifreeze function
OCF / OCF1 / OCF2
Antifreeze function option
Adjustment range: OFF / ON
Factory setting: OFF
CFR / CFR1 / CFR2
Antifreeze temperature
Adjustment range:
-40.0 … +10.0 °C [-40.0 … +50.0 °F]
Factory setting: +4.0 °C [+40.0 °F]
The antifreeze function activates the loading circuit between the collector and the
store when the temperature falls below the adjusted antifreeze temperature. This
will protect the uid against freezing or coagulating. If the adjusted antifreeze tem-
perature is exceeded by 1 K [2 °Ra], the loading circuit will be deactivated.
If the antifreeze function is activated, is displayed. If the antifreeze function is
active, and are displayed (ashing).
Note
Since this function uses the limited heat quantity of the store, the anti-
freeze function should only be used in regions with few days of tempera-
tures around the freezing point.
The antifreeze function will be suppressed if the store temperature falls
below +5 °C [+40 °F] in order to protect the store from frost damage.
Priority logic
Note
Priority logic can be used in 2-store system only (Arr = 4, 5, 6).
PRIO
Priority
Adjustment range: SE 1, SE 2, Su 1, Su 2, 0, 1, 2
Factory setting: Arr 4: 2, Arr 5, 6: 1
If a 2-store system has been selected, the priority logic determines how the heat is
divided between the stores. Different types of priority logic are adjustable:
spreaded loading (SE 1 and SE 2)
successive loading (Su 1 and Su 2)
parallel loading (0)
store sequence control (1 and 2)
If priority PRIO SE 1 or SE 2 (only available in Arr 6) is adjusted, the subordinate
store will be loaded in parallel to the priority store if the temperature difference
between the collector and the priority store (store 1 for SE 1, store 2 for SE 2)
exceeds the adjusted value DTSE and the subordinate store has not reached its
maximum temperature.
Parallel loading will stop as soon as the temperature difference between the collec-
tor and the priority store falls by 2 K [4 °Ra] below DTSE or the subordinate store
reaches its maximum temperature.
If priority PRIO Su 1 or Su 2 is adjusted, the stores are loaded successively. The
subordinate store will only be loaded if the priority store (store 1 for Su 1, store
2 for Su 2) has reached its adjusted maximum temperature (S1MX or S2MX).
60


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Sol Plus at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Sol Plus in the language / languages: English as an attachment in your email.

The manual is 3.79 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Remeha Sol Plus

Remeha Sol Plus User Manual - German - 72 pages

Remeha Sol Plus User Manual - Dutch - 72 pages

Remeha Sol Plus User Manual - French - 72 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info