6704.2007 TR10A041-C RE
7.4 MENU 4 – safety devices (see fig. 25 )
Display Function
Photocell
not present
present (with dynamic self-monitoring unit)
Closing edge safety device / leading photocell without
self-monitoring unit
not present
present
Closing edge safety device / leading photocell with
self-monitoring unit
present
Wicket door contact with self-monitoring unit
not present
present
ATTENTION
Safety devices without a self-monitoring unit
must be tested every 6 months.
Press the PRG button to return to normal operation
(menu 0).
7.5 MENU 5 – setting the advance warning phase,
options relay (accessories) and maintenance indi-
cation (see fig. 26 )
7.5.1 Maintenance indication
If the maintenance indication is activated (parameter A),
the operator lighting flashes at the end of a door cycle
when the prescribed maintenance interval - maintenance
of the door system - has been exceeded. The mainte-
nance indication can be reset by performing a learning
cycle.
7.5.2 Overview of maintenance intervals
Operator for single / double garages
Operation for 1 year or 2,000 door cycles
Operator for underground and collective garages
Operation for 1 year or 10,000 door cycles
Display Function
Advance warning phase / external with options relay
not active
5 seconds
10 seconds
Options relay (accessories)
not active
Relay clocks during advance warning phase
and door travel
Relay is switched on during door travel and
advanced warning phase
Relay picks up with the operator lighting. It is
switched on during the advance warning phase
when parameters 1-5 have been activated in
menu 2.
Relay is switched on during door travel
Relay picks up for one second when travel
or advance warning phase has started
e.g. a wipe impulse to switch on automatic
staircase lighting with 100 % duty cycle
Maintenance indication
not active
active
Press the PRG button to return to normal operation
(menu 0).
7.6 MENU 6 – force limit during operation in the
CLOSE direction (see fig. 27 )
In this menu, the sensitivity of the automatic force limit for
the closing cycle can be set (factory setting: parameter 4).
Note
Increasing the force value (parameter greater than 4) is only
possible if parameter 3 has been selected in menu J.
ATTENTION
Do not select an excessively high setting as
excessive force may cause damage to equip-
ment or injuries to persons.
For doors moving easily, a low value can be selected
if the sensitivity to obstructions is to be increased.
Press the PRG button to return to normal operation
(menu 0).
7.6.1 Checking the forces in the CLOSE direction
When changing the settings of menu 6, the forces as
defined in EN 12453 in the CLOSE direction must be
complied with; i.e. a subsequent check is absolutely
essential.