TDMA CONTROL 601/701:
11
Published 07/2007
Heat limit:
Night external temp:0..40 °C
If, during the day or night, the external temperature sen-
sor registers a temperature which exceeds the set tempera-
ture, the heating will switch off (heating circuit pump and
boiler are switched off). At 2K lower than the set tempera-
ture limit the heating will switch back on.
Frost Protection. External Temp Limit: -
10...+10 °C
When the external temperature falls below the set tem-
perature, the heating will be switched on, irrespective of
which operating mode is active. If the heating mode is off,
the pre-set inflow temperature (10
o
C) will be regulated.
Separate Heating Circuit Settings? Yes/No
ADVICE
This function is not available with the CONTROL 601,
since it can only regulate one heating circuit. The fol-
lowing input settings are found there under „Heating
Input“.
With the CONTROL 701 the separate heating circuits set-
tings can be entered under „Yes“ in the „Heating Circuit
Input 1 ...3“ menu point behind „Required room tempera-
ture“.
Daytime temperature drop
Night temperature drop
Override (Party Switch)
Operating mode
Heating off at 0..20 K
*
Temperature raising
*
Temperature lowering
*
Airing
*
*only with the setting „Room thermostat = Yes“
Daytime temperature drop:
On / Off
Night temperature drop
On / Off
The room temperature can be allowed to drop to a pre-set
temperature. The time period that after which the daytime
or night time temperature drop is allowed, and how long
for, are settable. The required room temperature is
achieved during the set time periods.
Night temp. Drop:
Each day/Daily/Wkends-Wkdays
Setting the time clock is carried out as described in para-
graph 2.4.1.
Example: Night Temp. Drop
Night Temp. Drop:
On
Time switch time:
Weekend/Weekdays
Weekdays On:
20:00
Weekdays Off:
06:00
Weekends On:
22:00
Weekends Off:
09:00
Required night time
room temperature:
16 °C
The night time temperature drop to 16
0
C, as set, is en-
abled between 20.00 and 06.00 on weekdays and be-
tween 22.00 and 09.00 at weekends.
Night Temp. Drop Override:
On / Off
If the override is switched to „On“ during the night time
temperature drop period, the night time temperature drop
period will be postponed until the override is switched
back to „Off“
The override can also be activated via the TR-CONTROL. If
the override is not switched back to off here, the night time
temperature drop will be reactivated the following night.
See also the TR-CONTROL Technical Documentation
Operating Mode:
Summer / Holiday / Winter
Summer Operation: Heating circuit pump and boiler are
switched off. Hot water back up heating is operational.
Heating circuit frost protection remains active.
Winter Operation: Heating circuit pump, boiler and hot
water back up heating are operational. Heating circuit
frost protection is active.
Holiday Operation: Heating circuit pump, boiler and hot
water back up heating are switched off. Heating circuit
frost protection remains active.
Room Thermostat Active
Yes / No
If a TR-CONTROL is connected to the CONTROL 601/70,
the integrated room thermostat can be activated via this
menu point.
Regulate the Heating Circuit via the TR-
CONTROL
The TR-CONTROL can be set to regulate the CONTROL
601/701 here. See the TR-CONTROL Technical Documen-
tation.
The following menu points are accessed after „Required
Room Temperature“ in the „Heating Circuit Input“ menu.
11


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Consolar Control 601 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Consolar Control 601 in the language / languages: English as an attachment in your email.

The manual is 5,12 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info