7 Problems and Solutions
Problem:
Cause:
Remedy:
Indicator
.. flashing and sensor fault indi-
cated.
Sensor is interrupted or short circuited.
Check sensor fitting and replace sensor if
necessary.
Regulator is not set correctly.
Check whether a function is activated even
though there is no sensor connected. Deac-
tivate the function.
Solar pump
. ... doesn’t run.
The regulator doesn’t switch the solar
pump on, even though there is sufficient
solar energy to store.
This may not be a fault! The regulator has
paused the solar pump operation as pro-
grammed. See the Technical Documentati-
on under „Solar Pump Operation“.
The solar pump is defective or is incor-
rectly installed.
Test the connection and replace the pump
if necessary.
... switches off because the tempera-
ture in the collector is too high, al-
though the upper thermal store tem-
perature has not reached 90 °C.
The flow volume has been incorrectly
set resulting in too high a difference
between the collector inflow and out-
flow temperatures.
Check the flow volume reading on the Ta-
cosetter or CONTROL601/ 701 (only if
using flow volume measuring to measure
yield). The flow volume must be set at 25
litres per hour and square meter.
Incorrect collector sensor securing. The
absorber temperature is incorrectly
measured.
The sensor should be fitted to the furthest
possible absorber plate, close to the ab-
sorber pipework, so that it receives the
same insolation levels. See also the instal-
lation instructions.
No hotwater
The regulator is incorrectly set.
Check the hot water temperature and time
programme and reset as necesssary.
Temperature sensor or thermal store
loading pump is defective.
Replace sensor or pump.
Heating system:
... Room temperature is too high
when the external temperature is
low or to low when the external
temperature is high.
Heating graph gradient or curvature is
incorrectly set.
Check the regulator settings and reset as
necessary.
...Rooms are cold even though the
boiler is running.
Heating pump is not functioning.
Check the connection and replace the
pump if necessary.
Regulator is incorrectly set.
See the Technical Documentation under
„Operating the Heating and Boiler“ Func-
tions.
If hot water demand has been priori-
tized, the thermal store is loaded as the
priority function and the heating circuit
mixer is switched off.
Deactivate the priority setting if not re-
quired.
Individual menu points or function
options do not show in the display.
The relevant function has not been cho-
sen.
If necessary, activate the function in the
System Variations menu.
62


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Consolar Control 601 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Consolar Control 601 in the language / languages: English as an attachment in your email.

The manual is 5,12 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info