Minimum Inflow Temperature:
0...120 °C
The minimum inflow temperature (for example with defined
boiler temperature) is entered here.
Mixer Regulating Parameter: 1...200
The mixer parameter is pre-ser at 100 (setting for the Con-
solar-Heating Circuit Mixer). A higher or lower setting
must be entered as appropriate to the installed mixer.
ADVICE:
The higher the entered regulating parameter the
quicker a deviation from the target temperature will be
corrected. However, using a parameter setting which is
too high can lead to the correct target temperature not
being achieved.
Safety Function in case of Mixer or Heating Circuit Pump
sticking: The regulator operates the heating circuit pump
for one minute a day and opens and closes the mixer
valve once. The safety function is activated if the heating
circuit pump has been switched off for longer than 24
hours.