4. Communication and interfacing
4.1. The VictronConnect App
The VictronConnect App communicates via Bluetooth. It is used for changing settings, monitoring the Lynx Smart BMS and up to
4 connected Lynx Distributors. For more information on the VictronConnect App see the VictronConnect manual.
4.2. GX Device and the VRM Portal
The Lynx Smart BMS can be connected to a GX device via VE.Can and the GX device in its turn can communicate with the VRM
portal. The GX device and the VRM will show all measured parameters, operational state, battery SoC and alarms.
4.3. Communication Lynx Distributor
Up to 4 Lynx Distributors can be connected to a Lynx Smart BMS. They communicate via the RJ11 cable. The Lynx Distributors
communicate fuse status and operational status to the Lynx Smart BMS. The Lynx Smart BMS can be used to read out the Lynx
Distributors, generate alarms in case a fuse is blown or communication is lost.
4.4. DVCC
DVCC allows the Lynx Smart BMS to control Victron Energy inverter/chargers, AC chargers and solar chargers via a GX device.
The Lynx Smart BMS will automatically adjust discharge current, charge current and charge voltage depending on the battery
state. For the action taken for each battery state, see below table.
DVCC is automatically activated. The following parameters are implemented:
Fixed parameters:
Absorption voltage is set at 14.2V
Storage/float voltage is set at 13.5V
Max charge current is set at 1C
Charge current at low cell voltage is set at 0.1C
User configurable via the VictronConnect app:
Absorption time
State of charge (SoC) threshold (A new charge cycle will be initiated as soon and the the battery state of charge drops below
this threshold)
Repeated absorption time (The number of days after which a new charge cycle is initiated, even though the battery state of
charge is still above the state of charge threshold)
For more information on DVCC and to find out which Victron Energy products can be controlled via DVCC, see the GX device
manual.
Table 1. DVCC action taken when certain battery conditions occur
Battery condition Allowed to
discharge
signal
Allowed
to charge
signal
DVCC action
A battery cell voltage is below
5°C.
This is a low temperature alarm.
High Low The charge current is reduced by lowering the charge
voltage to battery voltage minus 0.15V. This will
reduce the charge current to 0A.
The battery is signalling a low
voltage pre-alarm.
High High This is user selectable. Can be set to reduce the
discharge current to 0A, or to take no action.
A battery cell voltage is too low.
This is a under-voltage alarm
Low High The discharge current is reduced to 0A. Once the
under-voltage alarm is cleared it will be set back to
600A.
The charge voltage is reduced until the charge current
is 0.1C. Once the under-voltage alarm is cleared the
charge voltage will go back to 14.2V (28.4V).
Lynx Smart BMS
Page 7 Communication and interfacing
10


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Victron Lynx Smart BMS 500 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Victron Lynx Smart BMS 500 in the language / languages: English as an attachment in your email.

The manual is 3.23 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info