When the Lynx Smart BMS is switched off the following happens:
The ATC (allowed to charge) and ATD (allowed to discharge) signals are turned off, so that all loads and chargers are turned
off.
When the battery current is low enough the contactor will open so that the DC system is disconnected from the batteries.
The AUX terminal will de-power so that a connected GX device will also de-power.
The Lynx Smart BMS goes into hibernation mode.
Bluetooth will remain active.
There are 3 ways to operate the remote on/off feature:
Wire a switch between the remote-H and the remote-L terminal. When the switch is open the Lynx Smart BMS is off and will be
on when the switch is closed.
Present a High signal to the H terminal. If the H terminal is High (more than 2V) the Lynx Smart BMS switches on, and if the H
terminal is Low (less than 2V) the Lynx Smart BMS will switch off.
Present a Low signal to the L terminal. If the L terminal is pulled to ground the Lynx Smart BMS switches on, and if the L
terminal is free floating the Lynx Smart BMS will switch off.
3.4. Pre-charge circuit
The Lynx Smart BMS is equipped with a pre-charge circuit. This will pre charge capacitive loads such as inverters or inverter/
chargers before the contactor closes.
During pre-charge checks are performed. If the connected load is less than 20 Ohm, the current is too large or pre-charging takes
too long, the contactor will not close and an error will be generated.
If a pre-charge error has occurred, the Lynx Smart BMS will, after a wait time of 30 seconds, again try to perform a pre-charge. It
wil try this up to a maximum of 20 times.
3.5. Fans
The Lynx Smart BMS has two built-in fans. These turn on shortly during startup, when the loads are pre-charged.
In normal operation the fans will also turn on when:
The temperature exceeds 60°C (140°F).
The current exceeds 320A.
The dissipation in the contactor is too high (to prevent contactor overheating).
3.6. Battery Management System
Pre-alarm
The Lithium Smart battery sends a pre-alarm signal to the Lynx Smart BMS when one of its cell voltages drops below a set
threshold. The pre-alarm voltage threshold is set in the battery via the VictronConnect app. All batteries need to be set at the
same pre-alarm value.
When the Lynx Smart BMS receives a pre-alarm signal, it will activate its alarm relay and it will generate an alarm message. The
alarm message is generated at least 30 seconds before the loads are shut down via the ATD signal.
A requirement for pre-alarm to be active, is that batteries are used that support this feature. Older batteries did not have this
feature. To check if the battery is equipped with pre-alarm; connect to the battery with the VictronConnect app and see if the pre-
alarm feature is supported by the app. If the pre alarm setting is missing from the VictronConenct app, then the battery does not
support pre-alarm.
Allow-to-charge and Allow-to-discharge
The Allow-to-charge and Allow-to-discharge contacts control the chargers and loads in the system:
When the battery is fully charged and the battery voltage gets too high or the temperature is to low, the allow-to-charge contact
is opened and charging has to stop.
When battery voltage is low, the BMS adds a 30s delay before opening ATD if pre-alarm is not supported. An alarm message
will be sent immediately.
For this feature to operate correctly, it is essential that the loads and chargers are able to be controlled by the allow-to-charge and
allow-to-discharge signals. Ideally wire the signal to a devices remote on/off connector, or if that is not available a BatteryProtect
or Cyrix-Li relay can be used.
Contactor
If charging or discharging is not stopped and the battery voltage gets even higher or lower, the safety contactor will be opened to
disconnect the entire DC system to make sure the batteries are protected. This will only happen when the batteries are critically
low or when the batteries are overcharging.
Lynx Smart BMS
Page 5 Features
8


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Victron Lynx Smart BMS 500 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Victron Lynx Smart BMS 500 in the language / languages: English as an attachment in your email.

The manual is 3.23 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info