Vent Termination Below Grade:
Install Snorkel Kit #SLP-SNORK when it is not possible to
meet the required vent termination clearances of 12" (305
mm) above grade level. The snorkel kit will allow installation
depth of down to 7" (178 mm) below grade level. The seven
inches is measured from the center of the horizontal vent
pipe as it penetrates the wall. If the venting system is
installedbelowgrade,awindowwellmustbeinstalled
with adequate and proper drainage.
NOTE: Be sure to maintain side wall clearances and vent
run restrictions. Refer to Figures 2.3 thru 2.6.
1. Establish the vent hole through the wall.
2. Remove soil to a depth of approximately 16" (406 mm)
below the base of the snorkel. Install a window well (not
supplied). Rell the hole with 12" (305 mm) of coarse
gravel and maintain a clearance of at least 4" (102 mm)
below the snorkel, Figure 3.14.
3. Install the vent system as described in Figures 3.2 thru
3.14.
4. Be sure to make a watertight joint around the vent pipe
joint at the inside and outside wall joints.
5. Apply high temperature sealant around the inner and
outer snorkel collars. Join the pipes and fasten the
snorkel termination to the wall with the screws provided.
6. Level the soil to maintain a 4" clearance below the
snorkel.
7. If the foundation is recessed, use extension brackets
(not supplied) to fasten the lower portion of the snorkel.
Fasten the brackets to the wall rst, and then fasten to the
snorkel with self-tapping #8 x 1/2" sheet metal screws.
Extend the vent pipes out as far as the protruding wall
face, Figure 3.14.
Figure 3.14 - Use extension brackets to mount snorkel against
recessed wall.
ST219
snorkel detail
12/6/99 djt
Recessed Wall
Sheet Metal
Screws and
Bracket
Wall Screws
and Anchors
Waterproof Seal
Around Pipe
Firestop
Finishing
Collar
7" Pipe
Wall Plate
VerticalThrough-The-RoofApplication/Installation:
Note: Refer to Figures 2.8 thru 2.10 for restrictor plate
adjustments for vertical vent runs.
This gas stove has been approved for:
Vertical installations up to 40 feet (12 m) in height. Up to
a 10 feet (3 m) horizontal vent run can be installed within
the vent system using a maximum of two 90° elbows,
Figure 3.15.
Up to two 45° elbows may be used within the horizontal
run. For each 45° elbow used on the horizontal plane,
the maximum horizontal length must be reduced by 18"
(450 mm).
Example: Maximum horizontal length:
No elbows = 10' (3 m)
1 x 45° elbow = 8.5' (2.6 m)
2 x 45° elbows = 7' (2.1 m)
A minimum of an 8 feet (2.5 m) vertical rise is required,
Figure 3.15.
Two sets of 45° elbow o󰀨sets may be used within the
vertical sections. From 0 to a maximum of 8 feet (2.5 m)
of vent pipe can be used between elbows, Figure 3.16.
SLP-HVS supports o󰀨sets. This application will require
that you rst determine the roof pitch and use the
appropriate starter kit. (Refer to Venting Components
list.)
The maximum angular variation allowed in the system is
270°, Figure 3.16.
For the minimum height of the vent above the highest
point of penetration through the roof, Figure 3.16.
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Vermont Castings Intrepid - Gas at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Vermont Castings Intrepid - Gas in the language / languages: English as an attachment in your email.

The manual is 17.23 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info