6 SATEL Installer Manual
special "disarm under duress" alarm. Operation of the output can be restricted to alarms
from particular partition. The output can remain active for a specified time (from 01 to 99
seconds or from 01 to 99 minutes) or until the alarm is cleared by the user. During
operation, it can every second change its state (pulsate).
11 chime the output starts on violating the disarmed zones for which the “chime” option has
been activated. Operation of the output can be restricted to the selected "list of zones" or
to specified partition (identically as for the 01 output type). The output can remain active
for a specified time (from 01 to 99 seconds or from 01 to 99 minutes). If the LATCH option
(on until switch-off) is enabled for the output, it will be deactivated when the alarm is
cleared by the user. The output signals violations irrespective of whether the chime blocking
in the keypad is on or off (to enable the blocking, press and hold down the key [8]).
12 switch MONO the output is activated by calling the user function 7 ([CODE][
*
][7]) or using
a code with authority level 5 ([CODE][#]). Operation of the output can be restricted to
specified partition. The output can remain active for a time from 01 to 99 seconds or from
01 to 99 minutes (do not program the LATCH option for the output).
13 switch BI (ON/OFF) the output changes its state when the user function 8 ([CODE][
*
][8]) is
called or a code with authority level 6 ([CODE][#]) is used. Operation of the output can be
restricted to specified partition.
14 arm status the output is active in the armed mode. Operation of the output can be restricted
by selecting a "list of zones" or partition. Unless zones and partitions are selected, the
output is active when any partition (zone) is armed.
15 silent arm status the output is active in the silent armed mode. Operation of the output can
be restricted by selecting a "list of zones" or specific partitions.
16 exit delay statusthe output is active during the "exit delay" countdown by the control panel.
Operation of the output can be limited to indicating the "exit delay" for specified partition.
17 entry delay status the output is active during the "entry delay" countdown. Operation of the
output can be limited to selecting the "entry delay" for specified partition.
18 telephone usage status the output is active when the control panel is on the telephone line.
19 ground start the output is activated by the control panel if the GROUND START signal is to
be generate (a 2 sec. signal occurring before the control panel "lifts the handset" required
by a specific type of telephone exchanges).
20 monitoring confirmation the output activated for 3 seconds by the control panel, after
correct termination of the monitoring session.
21 bypass status – the output is active when some zones are bypassed in the system. Operation
of the output can be limited to showing the bypass of zones specified in the list of zones,
or the bypass of selected partition zones.
22 READY status the output is active when all the control panel zones are free from violations.
Operation of the output can be limited to showing the READY status of zones specified in
the list of zones, or the READY status of selected partition.
23 zone violation the output starts when one of the zones is violated. Operation of the output
can be limited to the selected "list of zones" or specified partition (identically as for the 01
output type). The output can remain active for a specified time (from 01 to 99 seconds or
from 01 to 99 minutes) or until the armed mode is deactivated or the alarm cleared.
24 telephone line trouble the output used when telephone messaging is doubled by radio
messaging; it makes possible reporting the telephone line trouble.
25 AC power loss.
26 battery trouble activated when the battery voltage in three consecutive tests drops to about
11 V.
27 power supply the output intended for powering detectors, radio lines and other equipment
with 12 V direct voltage. When programming this type of output, pay special attention to
permissible current-carrying capacity of each of the control panel outputs.
28 fire detectors power supply the output intended for powering the fire detectors.
The output closely interacts with the 24H fire” zones. If assigned to any of the control
8


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Satel CA-6 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Satel CA-6 in the language / languages: English as an attachment in your email.

The manual is 0,56 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Satel CA-6

Satel CA-6 Additional guide - English - 40 pages

Satel CA-6 Quick start guide - English - 8 pages

Satel CA-6 Additional guide - German - 19 pages

Satel CA-6 User Manual - German - 19 pages

Satel CA-6 Installation Guide - German - 80 pages

Satel CA-6 User Manual - German - 18 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info