4 SATEL Installer Manual
If one of the control panel outputs is programmed as the “fire detectors power supply”,
violation of the zone will actuate the alarm verification mechanism and will signal alarm in
the keypad. To perform the verification, control panel disconnects momentarily power
supply to the fire detectors and checks, whether after reconnection of power supply the
violation will be repeated within 90 seconds. If that’s the case, the control panel will send a
"zone alarm" message to the monitoring station, activate the “fire alarm” and “fire/burglary
alarm” outputs and trigger the fire alarm (intermittent signal) in the keypad.
If there are no "fire detectors power supply” outputs, the zone violation will immediately
send a "zone alarm" code to the monitoring station, activate the “fire alarm”
and “fire/burglary alarm” type outputs, as well as trigger the fire alarm (intermittent signal)
in the keypad.
12 armingviolation of this zone will arm the partitions the zone belongs to.
13 silent armingviolation of this zone will arm in silent mode the partitions the zone belongs to.
14 disarmingviolation of this zone will disarm the partitions the zone belongs to.
15 no alarm actionviolation of this zone will activate the “zone violation” type outputs.
16 arm/disarm violation of this zone will arm the partitions the zone belongs to, end of violation
will disarm those partitions.
17 delayed with signalling a delayed zone with the same function as the 01 type zone, but
with delay countdown signaling in keypads.
18 arming with bypass violation of this zone arms the partition the zone belongs to,
simultaneously bypassing the zones programmed as auto-bypass (see: FS16, FS19).
19 perimeter zone armed since entering the access code and confirming it with the [#] key
(i.e. arming the partition). Violation of this zone during countdown of the "exit delay" will
trigger an alarm.
Reaction time for each zone can be programmed within 0.016 s to 4.08 s. For delayed zones,
an individual time delay can be set. The zones can be selectively bypassed and/or assigned
to any partition. In case of messaging to the telephone monitoring stations, five event codes
sending to the monitoring stations can be determined for each zone.
The CA-6 has an additional CTL input, which is intended for arming or disarming. It can
also be used for connecting the panic, fire or emergency button.
Outputs
The CA-6 is equipped with 5 programmable outputs: 3 high-current (2.2 A) and 2 low-current
(50mA). The high-current OUT1, OUT2 and OUT3 outputs are protected by special electronic
fuses with current limiters set at 2.2 A. The control panel monitors presence of voltage,
overload, and signals trouble conditions at these outputs. When active and at positive
polarization, the above outputs will supply +12 V for the load.
The OUT4 and OUT5 outputs (low-current, 50 mA) control ground of the load when active
and at the positive polarization programmed (+12 V), these outputs are shorted to common
ground (0 V), whereas they are open when inactive.
The +KPD keypad supply output is fitted with an electronic fuse with current limiter 2.2 A.
All outputs are equipped with protection against inductive loads and pulse interference.
Assignment of the particular outputs can be restricted to the specific partitions/zones of the
system.
For each output can be defined the operation time in seconds (from 1 to 99 seconds),
in minutes (from 1 to 99 minutes), or LATCH type (until switch off). It is possible to determine
the output polarity for active state (+12 V or 0 V on the load), and whether it should operate in
pulsed or continuous mode.
Designation of the outputs can be adapted to the needs of the alarm system controlled by the
panel. Though individual outputs differ by their design, each of them can perform one of the
following functions:
6


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Satel CA-6 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Satel CA-6 in the language / languages: English as an attachment in your email.

The manual is 0,56 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Satel CA-6

Satel CA-6 Additional guide - English - 40 pages

Satel CA-6 Quick start guide - English - 8 pages

Satel CA-6 Additional guide - German - 19 pages

Satel CA-6 User Manual - German - 19 pages

Satel CA-6 Installation Guide - German - 80 pages

Satel CA-6 User Manual - German - 18 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info