ENGLISH
UNICO BOILER
Should the conditioner block and signal an error (as indicated in the following table), specify the LEDs that are ashing to the
service centre in order to facilitate the intervention (g. 24).
DESCRIPTION
LED D
GREEN
LED C
YELLOW
LED B
GREEN
LED A
RED
MASTER unit internal exchanger overtemperature (HTI) OFF OFF
ON
OFF
MASTER unit external exchanger overtemperature (HTE) OFF OFF
ON ON
MASTER unit outdoor temp. probe fault (short circuit) (TFS7) OFF
ON
OFF OFF
MASTER unit outdoor temperature probe fault (open circuit) (TFS8) OFF OFF OFF
ON
MASTER unit internal fan malfunction (SV) OFF
ON
OFF
ON
MASTER unit insufcient exchanger temperature (CF/RL) OFF
ON ON
OFF
MASTER unit condensation water maximum level (OF) OFF
ON ON ON
MASTER unit EEprom parameters not valid (CKS)
ON
OFF OFF OFF
MASTER unit ambient temperature probe fault (short circuit) (TFS1)
ON
OFF
ON
OFF
MASTER unit ambient temperature probe fault (open circuit) (TFS2)
ON
OFF
ON ON
MASTER unit internal exchanger temperature probe fault
(short circuit) (TFS3)
ON ON
OFF OFF
MASTER unit internal exchanger temperature probe fault
(open circuit) (TFS4)
ON ON
OFF
ON
MASTER unit external exchanger temperature probe fault
(short circuit) (TFS5)
ON ON ON
OFF
MASTER unit external exchanger temp. probe fault (open circuit)
(TFS6)
ON ON ON ON
WALL unit malfunction
ON
OFF OFF
ON
: ashing
WARNINGS SIGNALLED DURING NORMAL OPERATION SHOULD NOT BE INTERPRETED AS ANOMALIES.
LED A: indicates the lter may need cleaning
After this operation the LED must be switched off manually as indicated in section 2.4.1
LED B steady light: high battery temperature signal.
LED A + LED C ashing: continuous pump operation.
If the UNICO BOILER WALL unit malfunctions, the UNICO BOILER MASTER can be run temporarily on its own. To clear the alarm
status and enable the UNICO BOILER MASTER unit on its own, proceed as follows: cut the mains voltage to both units, wait a
few seconds, and then reconnect the power line to the UNICO BOILER MASTER unit only.
Once the UNICO BOILER WALL is working correctly again, simply power it again and it will be detected by UNICO BOILER
MASTER.
2.1.13 Evacuating condensate water during an emergency (g. 25)
If there should be a malfunction in the condensation water drain system, the air conditioner stops working and signals, with ashing
orange, green and red lights (the second and third LEDs from the left), the alarm status.
To enable the air conditioner to work temporarily until the service personnel arrive, you can drain the water out by following these
simple instructions:
- remove the lower cover (g. 25 ref. A)
- remove the cap (g. 25 ref. B) after having placed a good-sized container underneath it (at least 5-liter capacity) to collect the
water (see g. 25)
- after having cleared the fault, the service personnel will close the evacuation pipe.
2.2 UNICO BOILER WALL INSTALLATION PROCEDURES
2.2.1 Instructions for installation
To obtain the best results and optimum performance, follow the instructions for correct installation provided in this manual.
Failure to follow the instructions and apply the rules indicated may cause malfunction of the appliance and relieves the manufacturer,
OLIMPIA SPLENDID of any form of guarantee and liability for damages to persons, animals or property.
The electrical system must comply with the regulations and rating data in the technical sheet, with good grounding.
2
43


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Olimpia Splendid Unico Boiler at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Olimpia Splendid Unico Boiler in the language / languages: English, German, French, Italian, Spanish as an attachment in your email.

The manual is 21,81 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info