ENGLISH
2
- close the protection of the board (g. 21 ref. A)
- ret the front cover of the machine with the six screws
- ret the two wedged-in covers (upper and lower).
CAUTION: these operations should be performed with the machine already positioned on the bracket. Read the instructions
carefully before completely the electric connection.
2.1.11 UNICO BOILER MASTER CONFIGURATION, TOP/BOTTOM INSTALLATION (FIGS. 22, 23)
This unit may be installed either at the bottom of the wall (adjacent to the oor) or at the top (adjacent to the ceiling). The air jet
can be modied to optimize air distribution and room well-being by changing the position of the air outlet ap.
Figure 22 refers to a machine congured for installation near the oor in which air ows upwards. The same conguration may also
be used to install the unit near the ceiling with the cooling function. This permits to increase the air ow inside the room (Coanda
effect).
Figure 23 refers to a machine congured for installation near the ceiling in which air ows downwards.
OPERATION TO BE PERFORMED WHEN THE MACHINE IS SWITCHED OFF AND THE POWER SUPPLY IS DISCONNECTED.
CHANGING THE CONFIGURATION OF THE AIR OUTLET FLAP FROM BOTTOM TO TOP OF WALL
- delicately open the air outlet ap
- unhook the ap (side and central hooks on the bafes) (g. 22)
- remove the pin (g. 22 ref. A)
- turn the ap 180° (g. 22)
- insert the pin (g. 23 ref. A) on the right-hand side of the ap
- insert the ap into the machine by inserting the pin (g. 23 ref. B) into the top hole that is on the right-hand side in the opening
(g. 23 ref. C), and the ap’s left-hand hole on the upper pin that is on the left-hand side in the opening (g. 23 ref. D).
CHANGING THE CONFIGURATION OF THE AIR OUTLET FLAP FROM TOP TO BOTTOM OF WALL
- delicately open the air outlet ap
- unhook the ap (side and central hooks on the bafes) (g. 22)
- remove the pin (g. 22 ref. A)
- turn the ap 180° (g. 22)
- insert the pin (g. 23 ref. A) on the right-hand side of the ap
- insert the ap into the machine by inserting the pin (g. 23 ref. B) into the bottom hole that is on the right-hand side in the opening
(g. 23 ref. C), and the ap’s left-hand hole on the lower pin that is on the left-hand side in the opening (g. 23 ref. D).
After having performed the mechanical operations to change the air outlet ap position, it is necessary to congure the control
electronics of the machine by following the instructions listed in the paragraph Operating tests and anomaly diagnosis.
IMPORTANT: FOR CORRECT OPERATING OF THE APPLIANCE, EVERY TIME THAT THE CONFIGURATION OF THE AIR
OUTLET FLAP IS MODIFIED, THERE MUST ALWAYS BE A CORRESPONDING RESPECTIVE ELECTRONIC CONTROL
SETTING.
2.1.12 UNICO BOILER MASTER running tests and troubleshooting (g. 24)
The conditioner is able to perform a brief auto-diagnosis cycle to check that the internal components are operating normally and
during which it is possible to perform the conguration of the electronic control based on whether installation of the appliance was
performed to the upper part (to the ceiling) or lower part (to the ground) of the wall.
To activate the self-diagnosis function, proceed as follows:
- power the appliance by connecting it to a socket or by acting on the master switch of the system;
- ensure that the machine is on stand-by (no LED should be lit on the console);
- Press the micro-key positioned underneath the hole to the left side of the console (g. 24 ref. H) with a pointy object for at least
10 seconds. The acoustic signal emitted indicates that the self-diagnosis function has been activated.
At this point the current conguration of the machine will be displayed for a few moments as indicated below:
LED A (red) on: appliance tted with heat pump function;
LED B (green) on: installation to the lower part of the wall (to the ground) (factory installation);
LED C (yellow) on: installation to the upper part of the wall (to the ceiling);
LED D (green) on: reset settings function after an active black-out (factory setting).
Then, all of the LEDs on the console will start ashing simultaneously for 10 seconds. During this phase, through the micro key
(g. 24 ref. H), it is possible to modify the previously displayed setting related to the type of appliance installation.
NB: Conguration of the electronic control for installation at the top of the wall causes an automatic correction of the ambient
temperature reading in heating mode of 3°C.
At this point the self-diagnostic function activates the appliance in heating mode (if tted with the heat pump function) for approx.2
minutes and then in cooling mode for another 2 minutes.
It is possible to terminate the function prematurely simply by switching the appliance off using the remote control.
42


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Olimpia Splendid Unico Boiler at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Olimpia Splendid Unico Boiler in the language / languages: English, German, French, Italian, Spanish as an attachment in your email.

The manual is 21,81 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info