12.0 Troubleshooting (continued...)
10.0
11.0
12.013.0
Common Installation Faults
For optimum performance, this unit must be correctly sized to
match the heat loss requirements of the space it is required to
heat, and the heating system must be correctly designed to
provide adequate flow of hot water to the unit (refer to section
2). If the recommendations in section 2 are not followed,
problems may arise as detailed below.
Heating Mode -
No Fan
Heating Mode
poor heating
performance and/or
unit cycles on low
limit thermostat
Possible Causes
Unit switched off
Temperature set point reached
Unit not switched on at fused spur
Fuse blown at fused spur
Unit isolating valves shut
Water temperature reaching fan
convector below 43°C
Problem Remedy
Low water temperature to unit Turn up boiler thermostat
Poor water flow
Heating Mode
poor heating
performance and/or
unit cycles on low
limit thermostat
Possible Causes
Boiler thermostat set too low
Lack of flow to fan convector -
Pump set on low setting
Isolating valves not fully open
System incorrectly balanced with unit starved of hot water flow
Pipe sizing to unit too small
Problem
Poor heating
performance
Unit incorrectly sized for heat loss of room
13.0 Maintenance
Before undertaking any maintenance activity isolate the
electrical supply.
Maintenance should be restricted to occasional removal of dust
and lint around the unit. The outer surface may be wiped over
with warm water and mild detergent taking care to avoid water
entering the grille areas.
Turn on
Turn up room thermostat (if fitted)
Switch on at spur
Replace fuse
Open valves
Check boiler -
Programmer ON
Boiler ON and set to high with central
heating pump running
Vent air from heating system
If the fan convector is still faulty after checking the above, call your installer or MYSON Service.
xxxxxx HiLine LV manual_Layout 1 27/06/2011 09:39 Page 8
7


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Myson HI-LINE LV Fan Convector 7-4 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Myson HI-LINE LV Fan Convector 7-4 in the language / languages: English as an attachment in your email.

The manual is 0,08 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info