HI-LINE LV Fan Convector
1.0 General Information
2.0 Heating System Design
l This HI-LINE LV fan convector is designed for wall-mounted
installation with a maximum installation height of 2.13m to
the underside of the unit and a minimum clearance between
the top of the unit and the ceiling of 50mm.
l The minimum installation height to the underside of the unit
is 1.8m.
l The minimum side clearance is 100mm.
l The HI-LINE LV should only be used on closed circulation, two
pipe, pump assisted central heating systems.
l Before proceeding with the installation, the heating system
design must be considered and the unit correctly sized to
meet the heat loss requirements of the room at normal fan
speed.
l This unit is supplied with a fan speed selector switch giving
two fan speed options and off.
l This unit is fitted with a 12V transformer that enables the unit
to be fitted in a bathroom. The unit must be positioned in
accordance with local or national wiring regulations.
l This HI-LINE LV unit can be controlled by the addition of a
remote room thermostat. In bathroom installations this must
be connected to the low voltage circuit, and positioned in
accordance with local or national wiring regulations.
l This unit should not be installed in locations with ceiling
heights greater than 3m.
l This appliance is not intended for use by persons (including
children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they
have been given supervision or instruction concerning use of
the appliance by a person responsible for their safety.
l Children should be supervised to ensure that they do not play
with the appliance.
This fan convector must be fitted on a two pipe, pumped
circulation heating system.
For optimum fan convector heating performance the system
must be capable of providing sufficient hot water through the
heat exchanger. This means that:
1. The minimum pipe size from boiler to fan convector must be
at least 15mm.
2. This unit is not suitable for use on microbore pipe-work.
3. Where the unit is fitted on to a system with other emitters a
separate circuit for the fan convector should be considered
to provide adequate water flow.
4. The system water must be above 43°C for heating mode.
5. This unit is NOT suitable for one-pipe systems.
6. Optimum performance will require effective balancing of
the whole system.
7. This unit should NOT be used to replace a radiator in an
existing system unless an adequate flow of water can be
guaranteed.
3.0 Unit Selection/Sizing
Heat output performance is given in the Technical Data section
of this manual. This unit has two fan speed options, however, it
is important to size the unit to match the calculated heat loss
requirements of the room with the unit operating on the low fan
speed. The higher fan speed can then be used for more rapid
heating from cold in extreme conditions.
4.0 Location
l This HI-LINE LV unit may be fitted to any convenient wall at a
height from floor level that suits the application, providing an
unimpeded flow of warm air into the area to be heated.
l The maximum distance from the underside of the unit to floor
level is 2.13m.
l The minimum installation height to the underside of the unit
is 1.8m.
l This unit should not be installed in locations with ceiling
heights greater than 3m.
l The unit should be mounted on a flat wall, and stud or
partition walls should be avoided to minimize the possibility
of noise transmission.
l This unit may be fitted in zone 2 or the outside zones of
a bathroom, in accordance with local or national wiring
regulations (see fig 1) .
1.02.03.04.0
Zone 1 Zone 2
Zone 2
Zone 0
OUTSIDE ZONES
3m
2.25m
0.6m
0.6m
Fig. 1
xxxxxx HiLine LV manual_Layout 1 27/06/2011 09:39 Page 4
3


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Myson HI-LINE LV Fan Convector 7-4 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Myson HI-LINE LV Fan Convector 7-4 in the language / languages: English as an attachment in your email.

The manual is 0,08 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info