MI3002 MI3100 MI3102 Reduced low voltage supply systems
101
Trip-out time
Complete measurement range corresponds to EN61557-6 requirements. Specified
accuracies are valid for complete operating range.
General (non-delayed) RCDs
Measuring range (ms) Resolution (ms) Accuracy
0 ÷ 300 (½×IΔN, IΔN) 1
0 ÷ 150 (2×IΔN) 1
0 ÷ 40 (5×IΔN) 1
±3 ms
Selective (time-delayed) RCDs
Measuring range (ms) Resolution (ms) Accuracy
0 ÷ 500 (½×IΔN, IΔN) 1
0 ÷ 200 (2×IΔN) 1
0 ÷ 150 (5×IΔN) 1
±3 ms
Test current ...................................... ½×IΔN, IΔN, 2×IΔN, 5×IΔN
5×IΔN is not applicable for IΔN100 mA (RCD types AC,A)
2×IΔN is not applicable for IΔN500 mA (RCD type AC) or IΔN300 mA (RCD type A)
IΔN is not applicable for IΔN=1000 mA (RCD type AC) or IΔN500 mA (RCD type A)
Trip-out current
Trip-out current (IΔN=10 mA)
Measurement range corresponds to EN61557-6 requirements. Specified accuracies are
valid for complete operating range.
Measuring range IΔ Resolution IΔ Accuracy
0.2×IΔN ÷ 1.1×IΔN (AC type) 0.05×IΔN ±0.1×IΔN
0.2×IΔN ÷ 2.2×IΔN (A type) 0.05×IΔN ±0.1×IΔN
Trip-out current (IΔN30 mA)
Measurement range corresponds to EN61557-6 requirements. Specified accuracies are
valid for complete operating range.
Measuring range IΔ Resolution IΔ Accuracy
0.2×IΔN ÷ 1.1×IΔN (AC type) 0.05×IΔN ±0.1×IΔN
0.2×IΔN ÷ 1.5×IΔN (A type, IΔN
30 mA)
0.05×IΔN ±0.1×IΔN
Trip-out time
Measuring range (ms) Resolution (ms) Accuracy
0 ÷ 300 1 ±3 ms
Contact voltage
Measuring range (V) Resolution (V) Accuracy
0.0 ÷ 9.9 0.1 (-0 % / +15 %) of reading +
2 digits
10.0 ÷ 99.9 0.1 (-0 % / +15 %) of reading
101


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Metrel MI 3102 BT - Eurotest XE at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Metrel MI 3102 BT - Eurotest XE in the language / languages: English as an attachment in your email.

The manual is 1.18 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Metrel MI 3102 BT - Eurotest XE

Metrel MI 3102 BT - Eurotest XE User Manual - Dutch - 33 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info