MI3002 MI3100 MI3102 Reduced low voltage supply systems
99
Figure C.3: RCD contact voltage test
C.3.3 Line resistance and prospective short circuit current
Measured resistance represents Line-Line resistance (RL1-L2). Nominal system voltage
for calculation of IPSC is set to 110 V.
Nominal system voltage range for line resistance measurement is 90 V to 121 V. If input
voltage is out of range it is displayed on terminal voltage monitor, together with the
indicator of disabled test .
C.3.4 Fault loop resistance and prospective fault current
Definition of nominal system voltage for calculation of IPFC is changed to:
55 V for single-phase center-tap system selected,
63 V for three-phase system selected.
Tests can be carried out for both combination L1-PE and L2-PE. Each individual test
result is accompanied with appropriate indication.
Nominal input voltages are:
Nominal input voltage UN Voltage range
Single-phase 55 V system (44 V U < 61 V),
Three-phase 63 V system (56 V U 70 V),
If input voltage is out of range it is displayed on terminal voltage monitor, together with
the indicator of disabled test .
99


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Metrel MI 3102 BT - Eurotest XE at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Metrel MI 3102 BT - Eurotest XE in the language / languages: English as an attachment in your email.

The manual is 1.18 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Metrel MI 3102 BT - Eurotest XE

Metrel MI 3102 BT - Eurotest XE User Manual - Dutch - 33 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info