7. Wiring of external devices
In addition to using wireless items, which are part of the JA-60 system, hard wired devices can be wired to the system.
The JA-60 control panel (JA-60K) and the JA-60N detector are both equipped with terminals for wiring.
7.1. Terminals in the control panel
There are terminals in the JA-60K for use when wiring in external devices:
TMP terminals used for connecting a tamper switch of an external device. This input must be equipped with end of line
2.2 kOhm resistor. If the line resistance changes in ±30 % or more, the control panel concludes that the tamper is
broken.
PGX is an output (opened collector of a switching transistor to GND, max. 12V, 100mA). The function of this output is de-
termined by the setting of parameter 23x in the programming mode (see 8.6). The control panel also wirelessly trans-
mits the PGX signal and unit UC-216 can be used as a remote output of this signal (see 19.).
PGY is an output (opened collector of a switching transistor to GND, max. 12V, 100mA). The function of this output is de-
termined by the setting of parameter 24x in the programming mode (see 8.6). The control panel also wirelessly trans-
mits the PGY signal and unit UC-216 can be used as a remote output of this signal (see 19).
C is a common contact of the alarm output relay, max. load 60V / 1A,. The relay is turned on during any alarm of the
control panel.
NC is a normally closed contact of the alarm output relay.
NO is a normally open contact of the alarm output relay.
GND is a common ground terminal of the power output (-).
SIR is an external siren output. In the normal mode, it has a +U voltage. In the alarm mode it has a GND potential. Con-
nect an ordinary external siren to +U and SIR terminals (max. load 1A). A back up siren charging input should be con-
nected to the GND and the SIR terminals (during an alarm, the charging will temporarily halt).
+U is a back up +13.8V power output. The permanent load should not be higher than 50mA. A short time consumption
from this output can be up to 1A (max. 10 minutes). This output is fused and supervised by the control panel. If it is
overloaded, a control panel failure will be indicated (fault C).
AC a pair of terminals to connect the AC adapter DE-12-15 cable (15 VAC) – arbitrary polarity
1234 four small sized terminals of the digital bus – to wire JA-60E keypad when used (the same number terminals in the
control panel and in the keypad should be connected)
Fig.14
Alarm system JA-60 "COMFORT" - 10 - MDY51319
10


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Jablotron JA-60 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Jablotron JA-60 in the language / languages: English as an attachment in your email.

The manual is 2 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Jablotron JA-60

Jablotron JA-60 Additional guide - English - 1 pages

Jablotron JA-60 User Manual - English - 6 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info