Each path should consist of Hunter Industries Model
IDWIRE1 or IDWIRE2 color-coded decoder wire. This is
a twisted, solid-core wire suitable for direct burial, and is
always color-coded red and blue.
All red/blue connections in the two-wire path must be
made with DBR6 waterproof connectors or equal.
Each path has a red and a blue terminal with its number on
the decoder output module.
1. Route decoder path wires through the conduit into
the wiring compartment. Leave adequate slack in the
wires for thermal contraction.
2. Strip ½" (13 mm) of insulation from the red and blue
ends.
3. Connect the red wire to the red 1 terminal, and the
blue wire from the same pair to the blue 1. Repeat
for any other paths as needed.
Do not connect the paths in a loop, or back to any other
point in the controller. Leave the red and blue paths
separate at the end of each two-wire run. Simply insert
decoders in the path until complete, and stop at the
last decoder on the path. If this is not possible, simply
cap each of the ends of the two wire path with a DBR6
waterproof connectors or equal.
Do not connect a wire path from one controller to another
controller!
When a decoder output module is installed, the controller
facepack will recognize it and the station size will change
to 99 (regardless of how many stations are in use). This
will also unlock the normally Extended Decoder displays in
the following dial positions. See DECODER OPERATIONS
(ACC99D VERSIONS) on page 56 for more information.
Key ConneCTIons .......................................................................
1. Common Ground Terminals (x 3) For return wires
(often white) from stations and master valves. Field
wiring may be returned to any of these 3 terminals
2. P/M1 Pump/Master Valve output 1, and status light
(return Pump/Master valve circuit to any of the 3 Com
common terminals). Output is 0.320 Amps max
3. P/M2 Pump/Master Valve output 2, and status light
(return Pump/Master valve circuit to any of the 3 Com
common terminals). Output is 0.320 Amps max
4. Hardwire terminal connection cover Remove
to install optional ACC-HWIM for hardwired
communications.
5. 24VAC Always-on 24V test terminal, for locating
valves in the field. Can also be used to power low-draw
sensor receivers such as Hunter WRC. Output is 0.420
amps maximum
6. Flow Sensor connections (+ and -) Connections for
Hunter HFS flow sensor
7. ET connections (+ and -) Not used. Connections for
Hunter ET Sensor only. If upper ET terminal is colored
red, Master Module requires update for use with ET.
8. If Master Module has a sticker that says ET Ready, or
if the version number of the module is 4.0 or later, the
Master Module is ET ready
9. Sensor Connections (1-4) Connections for up to 4
Clik-family sensors, or other normally closed switch
contacts
1
3
2
4
5
67
8
20


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Hunter ACC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Hunter ACC in the language / languages: English as an attachment in your email.

The manual is 7,53 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Hunter ACC

Hunter ACC User Manual - German - 108 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info