ConneCTInG The masTer ValVe(s) and/or pump sTarT relay(s)
The Pump/Master valve connections are located in the
upper right of the Master Module, which is in the upper left
corner of the controller itself.
Locate the P/M1 and P/M2 screw terminals on the Master
Module. These outputs are designed to supply 24 VAC,
0.320 A max, for a single Master Valve solenoid or a Pump
Start Relay (or Relay Booster).
The return wire from each P/M device (solenoid or relay)
must be connected to one of the COM terminals on the
lower terminal strip of the Master Module.
Connect one output wire from each Pump relay or Master
Valve solenoid to the desired 24 VAC P/M terminal.
Connect the return wire to one of the terminals marked
COM immediately below the P/M outputs.
Configuration of the P/M terminals is covered in the
Set Pump Operation section of the Programming and
Operations portion of this manual.
Up to 4 Hunter sensors can be connected to the ACC
controller, including:
Mini-Clik
®
Rain-Clik
(including Wireless Rain Clik)
Freeze-Clik
®
Mini-weather station
Hunter Flow-Clik
can also be connected, but it is
recommended that the HFS be used instead.
In the ACC controller, Clik sensors shut down individual
programs, not necessarily the entire controller. Each
sensor can be given its own response instructions by
program.
Hunter Clik sensors are usually normally closed, and open
on alarm. This signals the controller to suspend irrigation.
Other dry contact closure sensors can be used without
warranty, provided that a.) they require no voltage; and
b.) open the circuit when a shutdown condition is sensed.
Hunter makes no claims or representations that such
connections will be effective.
1. To connect Clik sensors, locate the SEN [1-4]
terminals on the Master Module (upper right corner
of controller).
2. Route the pair of wires from each sensor into the
cabinet through one of the low voltage conduit
openings in the bottom of the enclosure.
24 VaC TesT TermInal ................................................................
The Master Module features a “constant-hot” 24 VAC
output which can be used as a test point for locating
valves in the field:
1. After powering up the controller, attach the common
wire to the COM terminals as described above.
2. Touch each wire to the terminal marked 24 VAC to
identify the valve location.
3. Each valve will open electrically when the wire is
touched to the 24 VAC terminal.
4. After identifying the valve location, you may then
insert the wire into the appropriate terminal. This
feature allows you to sequence the valves in the
most logical order for the user without damaging the
controller by sparking the wires.
5. The 24 VAC terminal may also be used to power
wireless Clik sensor receivers. See Connecting a
Rain Or Freeze Shut Off Device on page 14 for more
information..
ConneCTInG a raIn or freeze shuT off deVICe .......................
21


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Hunter ACC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Hunter ACC in the language / languages: English as an attachment in your email.

The manual is 7,53 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Hunter ACC

Hunter ACC User Manual - German - 108 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info