18. Check gas leakage control and minimum gas
pressure switch (if installed); Parameter
must be set to a value greater than or equal to
8, depending on the connected options (see
section 13.2.13). Then set the gas leakage
control pressure switch to a switch pressure
equal to 50% of the inlet pressure. Check that
the measured inlet pressure is not the (higher)
closing pressure.
19. Return the boiler to ‘user level’ by pressing the
reset key.
20. Heat the system to approximately 176
o
F [80
°
C]
and switch off the boiler.
21. Bleed the system and check the water
pressure.
22. The boiler is now ready for operation.
23. Set the boiler controls to the required values.
24. Check all safety controls and ignition systems
for correct operation and safety shutdown
function.
25. Send completed commissioning reports to
DDR Americas Inc.
Note:
The Gas 310/610 ECO is supplied with a number of factory default settings that should be correct for most
installations. If there setting values are required: see sections 13.1 and 13.2.
The following operating situations are now possible:
26.
a. Modulating operation: The output of the boiler modulates on the basis of the flow temperature,
asked by the modulating control (see ‘Note’ in point 25c and section 8.6.2).
b. High/low operation: The boiler is operating at part load or full load, depending on the heat demand
(see section 8.6.5). on the safety boundaries the boiler is going to modulate.
c. On/off operation: the boiler modulates between minimal and maximum output on the basis of the
flow temperature pre-set on the boiler (see section 8.6.4).
d. Important!! The boiler will initially operate in forces part load. The factory setting for forced
part load time is 30 seconds. This setting is correct if modulating controllers are used (see point
25a). A forced part load time of 3 minutes is recommended for on/off operation (setting mode,
parameter
, see section 13.2.3).
e. 0-10 V operation: Depending on the adjustments, two situations are possible (see section 8.6.3):
The given off output varies linear with the sent signal, 2V = 20%, 10V = 100%
The given off flow temperature varies linear with the sent signal (depending on parameter
and
); example: 0V 32°F [0°C], 10V = 212°F [100°C].
The boiler modulates on the basis of the set flow temperature (setting range 68-194°F [20-90°C]
and a maximum
T protection.
Boiler gas ignition control operation and safety shutdown safety check procedure:
1. Shut off electrical power to boiler
2. Shut off main gas supply cocks valve to boiler
3. Restore power to boiler
4. Activate heat demand
5. Observe ignition
6. Observe safety shutdown condition, the boiler
shall shutdown then attempt to restart (max 5
automatic restarts, followed by lock-out code =
 and error on control, confirm shutdown
code is correct.
7. Reset the boiler control
8. Open main gas supply cocks valve
9. Observe ignition and note irregular ignition
consult maintenance section of this manual
45


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for De Dietrich Gas 310 ECO at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of De Dietrich Gas 310 ECO in the language / languages: English as an attachment in your email.

The manual is 3,76 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info