Before installation
For exhaust air mode always cut out
the protective grid in the air connector.
With exhaust mode, a backwash valve
should be installed unless it is already in -
corporated in the exhaust pipe or wall box.
If a backwash valve is not included with
your appliance, your dealer can supply you
with one (see accessories).
Installation backwash valve:
Insert the backwash valve in the mounting
openings on the air connector.
If the exhaust air is being routed
through the outside wall, a telescopic
wall box should be used.
Connecting to Ø100 mm exhaustair duct
Attach the reducing adapter (enclosed or
available from specialist dealer) to the air
outlet. Attach the exhaust-air duct to the
adapter.
Connecting to Ø120 mm exhaustair duct
Attach the exhaust-air duct directly to the
air outlet.
Exhaust-air mode
The exhaust air is discharged upwards
through a ventilation shaft or directly
through the outside wall into the open.
Exhaust air must not be discharged via a
smoke or exhaust gas flue which is already
in use or via a shaft which is used for venti-
lating rooms in which fireplaces are located.
Discharge exhaust air in accordance
with official and statutory regulations
(e.g. national building regulations).
Discharge of air into smoke or exhaust air
flues which are not in use requires the con-
sent of a heating engineer.
If the extractor hood is operated in
exhaust-air mode at the same time
as a flue-type heater
(e.g. gas, oil or
solid-fuel heater, instantaneous water
heater, boiler),
ensure that there is an
adequate air supply which the heater
requires for combustion.
Safe operation is possible provided that the
partial vacuum in the room in which the
heater is installed does not exceed 4 Pa
(0.04 mbar).
This can be achieved if the combustion air
is able to flow through non-lockable open-
ings, e.g. in doors, windows and in con-
junction with an air supply/air-intake wall
box or by other technical procedures such
as reciprocal interlocking.
If the air intake is inadequate, there is a
risk of poisoning from combustion
gases, which are drawn back into the
room.
An air-intake/exhaust-air wall box by itself
is no guarantee that the limiting value will no
be exceeded.
Note: When assessing the overall require-
ment, the combined ventilation system for
the entire household must be taken into
consideration. This rule does not apply to
the use of cooking appliances, such as
hobs and gas cookers.
The extractor hood can be used without
restriction in circulating air mode – with an
activated carbon filter.
Optimum efficiency of the extractor
hood:
q Short, smooth exhaust pipe.
q As few bends as possible.
q Pipe diameter as large as possible (ideal-
ly 150 mm dia.) and wide pipe bends.
If long, rough exhaust-air pipes, many
pipe bends or smaller pipe diameters are
used, the air extraction rate will no
longer be at an optimum level and there
will be an increase in noise.
q
Round pipes
Short exhaust air pipe:
inside diameter min. 120 mm,
Longer exhaust air pipe:
inside diameter min. 150 mm.
q
Flat ducts must have an inside
cross-section equivalent
to that of
the round pipes.
There should be no sharp bends.
ø 120 mm dia. approx. 113 cm
2
ø 150 mm dia. approx. 177 cm
2
q If pipe diameters differ, insert sealing
strip.
q Ensure that there is an adequate air sup-
ply for exhaust air mode.
120
150
120
150
120
150
36


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Constructa CD22130 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Constructa CD22130 in the language / languages: English, German, Dutch, French, Italian, Swedish, Spanish as an attachment in your email.

The manual is 9,07 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info