TDMA CONTROL 601/701:
17
Published 07/2007
Solid Fuel Boiler Tempera-
ture Sensor
(Art. N
o
. RE 046)
Minimum temperature
Solid Fuel Boiler Differ-
ence
Thermal Store Tempera-
ture Sensor –Solid Fuel
Boiler
(Art. N
o
. RE 046)
Solid Fuel Boiler Differen-
ce
Output: Solid Fuel Boiler (Pump)
2.6.3 Buffer Logic
This function enables the boiler to be switched off when the
buffer region of the thermal store has reached the heating
target temperature, whether this has been achieved from
solar energy or by using the boiler.
The buffer logic controls the boiler operation in relation to
the external temperature. The additional „lower buffer
temperature sensor“ which is situated below the „upper
buffer temperature sensor“ enables the boiler to run longer
in order to load the buffer region between these two tem-
perature sensors.
Buffer Logic
Difference : 2...24 K
This function enables the temperature difference to be set
by which the temperature in the heating buffer region
(„lower buffer sensor“ and „upper buffer sensor “) must be
higher than the heating target temperature before the
„boiler on/off“ function is activated.
Buffer Logic
Hysteresis : 1...10 K
The switch hysteresis for the buffer logic can be set here.
Function: Buffer Logic
The Input activates the output de-
pendant on
Boiler on/off out-
put
„lower buffer sensor“ and „upper
buffer sensor“ temperature
heating circuit inflow target tem-
perature 1 plus Buffer logic differ-
ence minus Hysteresis
Boiler On („Boiler
= on/off“ contact
= closed)
Hot Water Back up Heating acti-
vated
Frost protection active
„lower buffer sensor“ and „upper
buffer sensor“ temperature
Heating circuit inflow target tem-
perature 1 plus Buffer Logic Dif-
ference
Boiler Off („Boiler
= on/off“ contact=
open)
Heat limits exceeded
Example: Buffer Logic
Heatin Circuit Target Temperature:
50 °C
Upper Buffer Sensor:
48 °C
Lower Buffer Sensor:
42 °C
Buffer Logic Difference:
8K
Buffer Logic Hysteresis:
5K
When the upper buffer sensor and lower buffer sensor
reach a temperature of 58
o
C the „boiler on/off“ contact
is opened and the boiler is switched off. When the lower
buffer sensor and upper buffer sensor record a tempera-
ture of below 53 °C, the „boiler on/off“ contact is
closed and the boiler is switched on.
2.7 T-PRO
Main Menu 12:34
T PRO Input
The CONTROL 601/701 regulators have all-purpose tem-
perature difference regulating capabilities which enable
control of hydraulic switches of different types.
Temperature Sensor 2
Yes / No
If the „Temperature Sensor 2: No“ option is set then the T-
PRO will function as one temperature switch.
T- P R O Difference:
0...30 K
This function is used to set the temperature difference by
which the temperature at Sensor 1 (source) must be higher
than the temperature at Sensor 2 (sink) so that the „T-PRO
function is activated.
T P R O H y s t e r e s i s:
0...30 K
To prevent the contact switching continually on and off, the
switch hysteresis is set here.
T e m p e r a t u r e
m i n: 0...100 °C
T e m p e r a t u r e
m a x : 0...140 °C
Minimum or maximum values can be set for both tempera-
ture sensors (T-PRO Sensor 1 and 2) here.
T-PRO Extended Running:
0...60 Min.
The „T-PRO“ function will only be deactivated once the
pre-set extended running time has expired.
Use the T - P R O Time Switch:
Yes / No
If the time switch option „Yes“ is set the T-PRO will only be
active during the two set time periods.
T - P R O :
Each Day/Every Day/Weekend-
Weekdays
The time switch is set as described in paragraph 2.4.1.
Example: Temperature Difference Regulator
Temperature sensor T2:
Yes
T-PRO difference:
4K
T-PRO hysteresis:
2K
17


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Consolar Control 601 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Consolar Control 601 in the language / languages: English as an attachment in your email.

The manual is 5,12 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info