TDMA CONTROL 601/701:
16
Published 07/2007
Maximum: 2...50 k W
Boiler Capacity
The maximum boiler capacity for modulated boiler regula-
tion is set here.
0 V : 0...50 k W
Boiler Capacity
The boiler capacity at 0V can be set at this point.
10 V : 2...50 k W
Boiler Capacity
The boiler capacity at 10V can be set at this point.
P - P A R A : 0...50.0
Regulator Parameter
T n : 0...500.0 S e c
Regulator Parameter
The „P“ and „I“ parameters of the 0 to 10 volt output can
be set here.
Example: The thermal capacity of the Firma Giersch Giega
Star „Therme“ Boiler
(1) Boiler capacity max:
30 kW
(2) Boiler capacity min:
10 kW
(3) 0V:
0 kW
(4) 10V:
30 kW
P-Parameter:
10
I-Parameter:
15s
If the boiler target temperature is either exceeded or not
achieved the capacity of the „Therme“ will be decreased or
increased until the target temperature is reached.
ATTENTION:
Modulated boiler operation is only suitable for boilers
which set their operational capacity above 0 – 10V and
are not automonously modulated.
Pump Revolutions
minimum : 100 %
The minimum pump speed is set here. The boiler or ther-
mal store loading pump is controlled so that the target
boiler temperature is achieved. For modulated boiler op-
eration the pump speed of the loading pump is always
100 %.
Minimum running time
Boiler : 0...30 min.
The minimum boiler running time is set here, although the
maximum allowable boiler temperature will still activate
the safety shutdown.
Back up running time
Boiler pump: 0...20 MIN
The extended running time of the boiler pump is set here.
Extended running time
Thermal store pump: 0...20MIN
The extended running time of the thermal store loading
pump is set here.
ADVICE:
It is imperative to follow the operating instructions of
the boiler manufacturer when using the boiler regulat-
ing functions.
Boiler regulating: Input - Function – Output
Input
Function
Boiler temperature sensor
(Art. N
o
. RE 046)
Maximum temperature
Minimum temperature Boiler
pump
Thermal store loading pump
Output: Boiler on/off, Boiler or Thermal store loading pump
2.6.2 Solid Fuel Boiler Pump
Solid Fuel Boiler
Minimum Temperature:30...80°C
When the solid fuel boiler temperature sensor records the
minimum temperature the „solid fuel boiler“ function is ac-
tivated. The solid fuel boiler will run until the minimum
temperature is exceeded by 2K (the 2K hysteresis is set in
the factory).
Solid Fuel Boiler:
Difference: 2...24 K
This function is used to set the temperature difference by
which the solid fuel boiler temperature sensor must be
higher than the „solid fuel boiler thermal store temperature
sensor“ so that the „Solid Fuel Boiler“ function is activated.
The 2K hysteresis is set in the factory.
Boiler OFF when Solid Fuel Boiler ON?
Yes / No
If this function is set to „Yes“, then the boiler (e.g. oil or
gas) will switch off when the thermal store is being loaded
via the solid fuel boiler.
Solid Fuel Boiler Regulating: Input - Function – Output
Input
Function
16


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Consolar Control 601 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Consolar Control 601 in the language / languages: English as an attachment in your email.

The manual is 5,12 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info