4.5 Reversal limit
During operation of the gate in the CLOSE direction, the
system must distinguish between two possibilities: whether
the gate contacts the end stop (gate system stops) or an
obstruction (gate reverses direction). The limit range can be
adjusted as follows (see Figure9.4).
Setting the reversal limit:
1. Set DIL switch11 to ON.
The reversal limit can now be set step-by-step.
2. Briefly press print button P to decrease the reversal limit.
Briefly press print button T to increase the reversal limit.
During adjustment, the green LED will indicate the
following settings:
1× flashing
up to
Minimum reversal limit, the green LED
flashes once
10× flashing Maximum reversal limit, the green LED
flashes 10 times
3. Set DIL switch11 back to OFF to store the set reversal
limit.
4.6 Automatic timed closing
NOTE:
Automatic timed closing can only be activated if at least one
safety device has been connected. This is required according
to DINEN13241-1.
The hold-open phase can be set for operation with automatic
timed closing (see Figure 9.5).
Setting the hold-open phase:
1. Set DIL switch13 to ON.
The hold-open phase can now be set in increments.
2. Briefly press print button P to decrease the hold-open
phase.
Briefly press print button P to increase the hold-open
phase.
During adjustment, the green LED will indicate the
following settings:
1× flashing 30 second hold-open phase
2× flashing 60 second hold-open phase
3× flashing 90 second hold-open phase
4× flashing 120 second hold-open phase
5× flashing 180 second hold-open phase
3. Set DIL switch13 back to OFF to store the set hold-
open phase.
WARNING
Danger of injuries due to faulty safety equipment
In the event of a malfunction, there is a danger of injuries
due to faulty safety equipment.
After the learning runs, the person commissioning the
system must check the function(s) of the safety
equipment.
The system is ready for operation only after this.
5 DIL Switch Functions
The control is programmed via the DIL switches. Before initial
start-up, the DIL switches are in the factory settings, i.e. all
the switches are in the OFF position. Changes to the DIL
switch settings are only permissible under the following
conditions:
• The operator is at rest.
• The warning or hold-open phase is not active.
The DIL switches must be set as described below in
accordance with the national regulations, the desired safety
equipment and the on-site circumstances.
5.1 DIL switch1
Installation direction:
See Figure7.1
1 ON Gate closes to the right (as viewed from the
operator)
1 OFF
Gate closes to the left (as viewed from the
operator)
5.2 DIL switch2
Set-up mode:
See Figures 8.1a – c
The safety and protective devices are not active during set-up
mode.
2 ON • Teach-in gate travel
• Delete gate data
2 OFF
Normal mode
5.3 DIL switch3 / DIL switch4
SE1 safety device (opening):
See Figure9.6
The functions of the SE1 are set with DIL switch3 in
combination with DIL switch4.
3 ON Activation kit for closing edge safety device or
photocell with testing
3 OFF
• 8k2 resistance contact strip
• Photocell from another manufacturer
• No safety device (8k2 resistance between
terminals20 / 72, delivery status)
4 ON Brief, immediate reversing in the CLOSE direction
(for SKS)
4 OFF
Brief, delayed reversing in the CLOSE direction
(forphotocell)
34
C300 - C800 / Rev. 1.1 RE / 07.2014
ENGLISH
34


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Berner C500 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Berner C500 in the language / languages: English, German, Dutch, French, Italian, Spanish as an attachment in your email.

The manual is 12,56 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info