Heat pump water heater – INSTALLATION
36
4.3
Discharge of condensate
The condensate or water, which is formed in the outdoor unit during heating operation, must be eliminated, freely or
through the drain. Fix the drain connection into the hole which is located on the bottom of the unit and connect the
plastic tube with the connector. Ensure that the condensate water runs out in a suitable drain and make sure the
discharge is made without hindrance.
4.4 Tools for the connection of refrigerant lines
a) Group manometer suitable for use with R134a, with charge and vacuum tubes;
b) Vacuum pump;
c) Torque wrenches for nominal diameter of 1/4 “and 3/8” sizes on both sides to respond to the measures of the pipe
unions;
d) Flaring clamp ø nominal 1/4 “and 3/8”, equipped with a terminal receiving opening so that the projection of the
copper tube can be adjusted from 0 to 0.5 mm in the working folder ;
e) Pipe cutter;
f) Pipe reamer;
g) Leak Detector for R134a, a leak detector is used exclusively for HFC refrigerants. It must have a high detection
sensitivity, minimum 5g per year.
4.5 Preparing of the refrigerating pipes
WARNING! Before carrying out any installation check the following:
a) Use only copper tubes for air conditioners type (copper tubing for the refrigeration and the conditioning) or copper
pipes with proper insulation (at least 6 mm thick), suitable for use with R134a;
b) Never use piping with a thickness less than 0.8 mm;
c) Provide a path of the pipes as short and simple as possible (maximum length 8 m with 3 m of fall). Do not provide
a path that may obstruct the access to the cap and the removal of flange. See Figure 9.
d) Protect the pipes and cables to avoid damage;
WARNING! The re
frigerant lines, and fittings for connection must be insulated to avoid dangerous
burns, loss of performance and product malfunction. Ensure the insulating sheath of the tubes
through fastening clamps to prevent it from moving.
Remove the locking of the tubes shortly before making the connection: absolutely must prevent moisture or dirt from
entering. If a pipe is bent too often becomes hard: Do not bend more than 2 times in the same section. Unwind the
hose unwound without pulling (see fig. 8).
4.6 Connecting the internal unit
a) Shape the pipes according to the path;
b) Remove the brass plug on the indoor unit and store them (check that no impurities are left);
c) Cut the pipe to the fixed length, with a pipe cutter, avoiding any deformation;
d) Remove burrs with pipe reamer avoiding to get impurities inside (keep down the tube);
e) Insert the threaded brass flare nuts on the pipes in the correct direction;
f) Insert the tube into the flaring tool and make the flange at the end of the connecting pipe, as indicated in the table
(see fig. 10):
ø NOMINAL ø EXTERNAL THICKNESS mm
DIMENSION “A” mm
FLARING TOOL
DIMENSION “L” mm
FLARING TOOL
1/4
6.35
0.8
0 ÷ 0.5
1.8 ÷ 2.0
3/8
9.52
0.8
0 ÷ 0.5
2.5 ÷ 2.7
After confirming that there are no wrinkles or tears on the flare, connect the pipes using two spanners, being careful
not to damage the pipes. If the force is insufficient, then there will be leaks. Although the force is excessive, there may
be losses because it is easy to damage the flange. The safest method is to tighten the connection by using a spanner
and a torque wrench, in this case use the table:
ø
Pipe
Tightening torque [Kgf x cm]
Corresponding force (with 20 cm spanner)
6,35 mm (1/4”)
160
200
Wrist force
9,5 mm (3/8”)
300
350
Arm force
We recommend leaving a few inches of copper pipe, for any subsequent operations in near the taps.
36


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Ariston NUOS 200 SPLIT at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Ariston NUOS 200 SPLIT in the language / languages: English, Dutch, French, Italian as an attachment in your email.

The manual is 2,77 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info