Setting the supplementary electric heater or activating the boiler
Index - String
MIN
value
MAX
value
Parameter function
04
This parameter indicates which logic must be used to manage the supplementary electric heater; the
choice of logic is determined by the value set in this parameter so, depending on the value, the set-
tings are:
0 = no supplementary electric heater present on the unit
1 = supplementary electric heater present, but cannot be activated during hot domestic water produc-
tion
2 = electric heater activation command used as consent for activation of an external boiler
3 = supplementary electric heater present and active during hot domestic water production
4 = electric heater activation command used as consent for activation of an external boiler which can
also be used in supplementary mode
WARNING:
• on the SRP V1 units, it is ABSOLUTELY FORBIDDEN to set this parameter value at (3);
• to set the value at (4), the DHW accessory is needed.
Panel control configuration
Index - String
MIN
value
MAX
value
Parameter function
03
This setting configures the type of control applicable to the units; depending on the value decided for
this setting, the controls on the functioning mode (HEAT/COOL) and the unit on/off command will be
managed in the following way:
Set value 0:
• Setting functioning mode = set parameter 0
• ON/OFF control = from the panel on the machine
Set value 1:
• Setting functioning mode = set parameter 0
• ON/OFF control = from the remote panel
Set value 2:
• Setting functioning mode = set from remote contact
• ON/OFF control = from the panel on the machine
Set value 3:
• Setting functioning mode = set from remote contact
• ON/OFF control = from the remote contact
Enabling domestic water
Index - String
MIN
value
MAX
value
Parameter function
01
In the heat pump models, there is the possibility to produce hot water for domestic use; this produc-
tion has its own modifiable setting and its own band (parameters E, F user menu); with this parameter
you can make parameters E and F visible and usable. Remember that to guide the domestic water
production request, once the function has been activated you must use digital input ID6 (marked on the
electric card enclosed with the unit as TWS). Remember also that setting this parameter with a value of:
• 1, you ENABLE the domestic water function
• 0, you DISABLE the domestic water function
The CLOSED status of the clamp means the domestic water function is ACTIVE. This function is avail-
able from software version 3.7 (the software version is visible as a reading, with index E). The minimum
compressor functioning time, and the defrosting time, take priority over the production of domestic
water. From software version 4.2, when domestic water is activated the adjustment is automatically set
on the basis of the output temperature, regardless of the value of the parameter (0) in this menu.
Parameters only visible in heat pump models
Parameters only visible in models set for
hot domestic water productio
Parameters only visible in the models with DCP installed
Parameters only visible in bicompressor models
Parameters only visible in the models with inverter compressor
59


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Aermec MODUCONTROL at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Aermec MODUCONTROL in the language / languages: English, German, French, Italian, Spanish as an attachment in your email.

The manual is 3,21 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info