58
EN
IMDCFJ. 12.05 6343841_03
Setting heating FORCE-OFF
Index - String
MIN
value
MAX
value
Parameter function
30 °C 70 °C
The heat pumps check the working temperature (input or output), to which a safety threshold is con-
nected, and beyond which the compressor is switched off immediately and automatically; this threshold
is called FORCE-OFF.
Setting the safety threshold
Index - String
MIN
value
MAX
value
Parameter function
0,5 °C 20 °C
Temperature threshold above the force-off, which reactivates the start-up of the compressor after the
switching off for force-off.
Setting integral time
Index - String
MIN
value
MAX
value
Parameter function
0 s 999 s
The units possess an advanced logic for controlling the processed water temperature; the complete
check prevents the system arriving at a point of equilibrium at a higher or lower temperature compared
with the one set in the work setting. Remember that an increase in the integration time weakens the
effect of the integral control.
Setting derivation time
Index - String
MIN
value
MAX
value
Parameter function
0 s 120 s
Time within which the input water temperature is checked to estimate the load on the system; if the
band on the setting value is exceeded within this time, the unit will be activated.
Setting the anti-freeze threshold
Index - String
MIN
value
MAX
value
Parameter function
-50 °C 20 °C
In the units it is possible to set a threshold for the anti-freeze alarm; this value specifies at what tempe-
rature the anti-freeze alarm is activated. Remember that, to modify the anti-freeze threshold parameter,
the corresponding dip-switch must be activated (see the dip-switch configuration table).
Setting frost protection
Index - String
MIN
value
MAX
value
Parameter function
04
In the units, it is possible to set a safety control on the water output temperature; on the basis of the
value assigned to this parameter, the anti-freeze electric heater is managed as follows:
• value 0, anti-freeze electric heater absent;
• value 1, anti-freeze electric heater installed and working only with machine in heat or cool mode;
• value 2, anti-freeze electric heater installed and working also in standby, but switching on the pump;
• value 3, anti-freeze electric heater working in standby without the pump being activated;
• value 4, with external air temperature less than 3°C, the pump is activated for 2 minutes every 30, to
monitor the temperature of the water throughout the system.
Parameters only visible in heat pump models
Parameters only visible in models set for
hot domestic water productio
Parameters only visible in the models with DCP installed
Parameters only visible in bicompressor models
Parameters only visible in the models with inverter compressor
58


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Aermec MODUCONTROL at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Aermec MODUCONTROL in the language / languages: English, German, French, Italian, Spanish as an attachment in your email.

The manual is 3,21 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info