Commissioning
GREENSPRING CWi47 – 6 720 646 322 (2015/04)
▶Verify CO
2
readings in P2 mode.
Fig. 59 Adjusting P1 CO
2
level
If P2 CO
2
level is out of range:
Remove yellow painted #40 Torx cover from the front of
the gas valve (Fig.
59). A plastic #40 Torx screw will be
revealed.
Turning the plastic #40 Torx screw counter clockwise.
P2 CO
2
levels will decrease.
Turning the plastic #40 Torx screw clockwise.
P2 CO
2
levels will increase.
Fig. 60 Adjusting P2 CO
2
level
Verify both P1 and P2 CO
2
readings are within the ranges
specified in Table
19.
Repeat steps 1 and 2 as necessary until CO
2
values are
within the specified ranges.
As soon as the levels of CO
2
are correct, verify the values of
CO corresponds to the limits of the Table
19. If the values
exceed the limits, it is necessary to verify the ventilation
system and heat exchanger.
End of adjustments
Record the final values in Table 20.
Reassemble all parts in reverse order:
Return slotted screw cover to original position and tighten
the philips screw (Fig.
59).
Reinstall Torx protection cover (Fig. 60).
Remove CO
2
analyzer probe and reinstall flathead screw
with gasket in exhaust collar.
Press ON/OFF button to turn OFF the heater.
Press ON/OFF button to turn ON the heater.
Heater is ready for normal operation.
Note: This screw adjustment is very sensitive
and should be made in small increments. It
may take several minutes for readings to
stabilize.
6720608158-38.1AL
CO2 range (%)
Max. CO level
(measured)
Natural gas
Max. P1 8.1% - 8.9% < 200 ppm
Min. P2 2.0% - 2.6% < 30 ppm
Propane
Max. P1 9.2% - 10% < 250 ppm
Min. P2 2.0% - 2.6% < 30 ppm
Note: Values above are for controlled climate conditions.
Inputs such as gas pressure, heating value of the gas,
humidity and temperature of combustion air impact CO and
CO
2
values. Changes in these inputs can result in different
CO and CO
2
values on the same appliance.
Table 19 CO
2
& CO target numbers
Program CO
2
values measured Date
P1 ______________ %
P2 ______________ %
Table 20
42


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Worcester-Bosch GREENSPRING CWi47 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Worcester-Bosch GREENSPRING CWi47 in the language / languages: English as an attachment in your email.

The manual is 5,96 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info