813148
36
Zoom out
Zoom in
Previous page
1/68
Next page
Manual_S5_Airplus_2015_04_20 Page 36 / 68
© Wodtke GmbH - Tübingen. All Rights and Changes Reserved.Printed 04/2015 Part No. 950 976
Note: Depending on which programme is set on
the furnace, the following output ranges can be
set:
Programme P5: heating output H = 2.0 - 6.0 kW
The following indicators can appear on the display
during operation of the furnace:
Display
indicator
Meaning
Stand-By-Dot Furnace has been manually de-
activated via the I/O button. The I/0 button
must be pressed to activate the furnace. In
stand-by mode, the furnace is not operation-
ally ready for external controllers.
ON
ON start signal (displayed briefly upon activat-
ing the furnace)
The furnace was started and enters the
warm-up programme shortly after displaying
the programme and an internal test.
OFF
OFF stop signal (displayed briefly upon deac-
tivating the furnace)
The furnace was deactivated and enters the
fan stop delay G OFF.
P5
400
Indicates the programme and the programme
version (displayed for several seconds upon
starting)
P5 = Programme 2-6 kW
400 = Programme version 400, 401 = Pro-
gramme version 401 etc.
A
-15
WARM-UP PROGRAMME + indication of re-
maining duration in minutes
The furnace begins to throw in pellets, the ig-
niter element is started, the ignition is moni-
tored (after correctly warming up, the furnace
switches to the heating programme H). The
warm-up programme takes 15 minutes. The
display counts down by minutes.
AI
-15
WARM-UP PROGRAMME IN + display in
minutes
(blinks in alternation with G OFF). The fur-
nace is still in G OFF.
However, the furnace has registered that the
I/O button was pressed again. The furnace in-
dicates that it will automatically resume oper-
ation in x minutes (after G OFF elapses).
AI 11 = warm-up in 11 minutes.
H
...
HEATING PROGRAMME + display of ad-
justed output in kW
The furnace is in heating mode. H 6.0 = heat-
ing programme 6 kW.
R.M
2.0
Internal modulation on flue gas side + display
of output in kW
The flue gas temperature "TR" was
exceeded. The furnace is run at the
lowest output (2 kW) via the internal
control. Once the temperature low-
ers sufficiently, the furnace returns to
the heating programme H.
The temperature on the air volume
sensor was exceeded. The furnace
regulates to the lowest output (2 kW)
Once the temperature lowers suffi-
ciently, the furnace returns to the
heating programme H.
R
120
CLEANING PROGRAMME R + indication of
remaining duration in seconds
An automatic cleaning cycle of 120 seconds
is started after each hour of continuous oper-
ation in heating programme H. Pellet convey-
ance is reduced and the fan speed is in-
creased in order to reduce the pellet volume
in the burner pot and to centrifuge the flue
ash out of the burner pot.
G
OFF
FAN STOP DELAY (= furnace shut-down.
Duration 15 minutes)
The furnace shuts down. The fan runs for 15
more minutes in order to fully burn away the
remaining pellets and to remove the heating
gases. Attention: the furnace only actually
goes into Stand-By after G OFF when G OFF
does not blink in alternation with HE OFF or
TW OFF. In other cases, the furnace can /
will be automatically restarted after G OFF.
WA
...
Maintenance indicator (displayed briefly)
The furnace must be serviced. Display WA
0.1 = maintenance 0.1 d overdue
Display "Function not available"
This display appears if the desired button
function cannot be performed or has no func-
tion assigned.
HE
...
HEATING PROGRAMME EXTERNAL (only
possible with externally modulating controller)
The furnace is adjusted to the displayed out-
put via an external modulating controller.
e.g. HE 5.2 = heating programme external 5.2
kW
HM
2.0
HEATING PROGRAMME MINIMUM (only
possible with external controller)
The furnace is adjusted to lowest output (2
kW) via an external controller (via the
MIN/MAX input).
HE
OFF
HEATING PROGRAMME EXTERNAL (only
possible with external controller)
The furnace is shut down via an external con-
troller (via the ON/OFF input or BUS)
OF
Processing remaining time: the furnace was
shut down via an external controller (via the
ON/OFF input). The remaining time is dis-
played as a countdown in minutes, in alterna-
tion with the current operating state. This
function is only possible if the remaining time
was set to >0 (menu level 2).
PL
OPEN
Pellet drawer open.
The pivoting lid of the pellet container is
open. If it is opened for longer than 3 minutes
without interruption during furnace operation
(mode = A, H, HM, R.M, HE, G OFF), the fur-
nace goes into fault (PL, Err).
FT
OPEN
Combustion chamber door open.
The combustion chamber door is open. If the
combustion chamber door is opened for
longer than 1 minute without interruption dur-
ing furnace operation (mode = A, H, HM,
R.M, HE, G OFF), the furnace goes into fault
(FT, Err).
Only open combustion chamber door when
the furnace is not operating!
36


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Wodtke Easy.nrg S5 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Wodtke Easy.nrg S5 in the language / languages: English as an attachment in your email.

The manual is 6.01 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Wodtke Easy.nrg S5

Wodtke Easy.nrg S5 User Manual - German - 68 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info