Manual_S5_Airplus_2015_04_20 Page 23 / 68
© Wodtke GmbH - Tübingen. All Rights and Changes Reserved.Printed 04/2015 Part No. 950 976
8.3.3 "RS 485" Input (external BUS com-
munication) - Display Indicator HE
RS 485 - BUS input for activation/deactivation and
for modulation of furnace output via an external
heating controller equipped with compatible bus
communication (accessory). The "Bus" input must
first be switched active for use.
Fig. 37: RS 485 input
Priorities:
I/O button has first priority, MIN/MAX (external),
ON/OFF (external), R.M (internal) have priority
over bus. If the bus input is switched active, the
furnace no longer responds to the modulation in-
terface (modulation is automatically deactivated
as soon as BUS is activated) or to modulation
mode/time switch mode via BB-S5 (TC1). Notice:
a corresponding controller must be connected to
the "RS 485" input after activation, because other-
wise the furnace will go to "Bu ER1" and "HE OFF"
errors.
Activation of the RS 485 input: Only permitted for
specialist companies! Proceed as follows:
Press button 1 x change to menu level 1
Now hold + + buttons simultane-
ously for at least 3 seconds until "S" appears in the
display change to menu level 2
Now hold or buttons pressed until "Bu
OFF" indicator appears in the display.
Now press + buttons simultaneously un-
til "Bu ON" indicator appears in the display the
"RS 485" input (bus communication) is now
switched active.
Press button for at least 3 seconds return
to operating level
Currently, only the Paradigma Systa-Comfort is
available as a compatible bus controller acces-
sory. Please contact your designated dealer for
further information and finally observe the instruc-
tions included with the Systa-Comfort controller. In
order to connect the Systa-Comfort, a so-called
gateway must be switched between the controller
and the furnace board. See image below for instal-
lation location on the furnace:
1. Gateway (installation location Tmax < 50 °C)
bottom, rear furnace wall
2. Cable for furnace control (PG cable gland)
3. From external controller
Fig. 38: gateway position
Behaviour in case of disrupted BUS communi-
cation (Bu Er1)
If there is no communication between the main
board and the external controller via the bus for a
certain period of time, "HE OFF / G OFF" (normal
shutdown/burnout 15 minutes) alternates blinking
with "BU Er1." The furnace shuts off because the
bus communication has been disrupted (classifi-
cation as error class 2).
The "BuEr1" error is archived in the error memory
of the furnace. An automatic reset + restart occurs
as soon as the BUS functions again (without ac-
tively required intervention by the user, error is ar-
chived in furnace memory, however). The furnace
can only be manually started when there is a com-
munication disruption of the BUS ("HE OFF" / "Bu
Er1" state) if the BUS is deactivated first (see
above).
1
2
3
23


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Wodtke Easy.nrg S5 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Wodtke Easy.nrg S5 in the language / languages: English as an attachment in your email.

The manual is 6.01 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Wodtke Easy.nrg S5

Wodtke Easy.nrg S5 User Manual - German - 68 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info