WESTFIRE · WF35
10
UK
UNIQ 35
Standard
UNIQ 35
Pedestal
UNIQ 35
inset
Distance from front to centre of top flue exit n/a n/a 335mm
Distance from rear to centre of top flue exit 120mm 120mm n/a
Distance from floor to centre of external air intake 115mm 505mm 65mm
WESTFIRE WF UNIQ 35
Distance to combustible materials rear 200mm
Distance to combustible materials side 200mm
Distance to Combustible materials
Combustible materials should not be located where the heat dissipating through the walls of fireplaces or flues
could ignite it. Therefore when installing the stove in the presence of combustible materials due account must
be taken of the guidance on the separation of combustible material given in Building Regulations Approved
Document J and also in these stove instructions.
The minimum distances to flammable materials are specified on the EN 13240 plate on the back of the stove.
Hearth
The hearth should be able to accommodate the weight of the stove and its chimney if the chimney is not indepen-
dently supported.
The WESTFIRE UNIQ 35 stove has been tested and are suitable to be installed on a 12mm non-combustible plate such
as Westfire 12mm glass plates or 20mm slate plates. Installation of all hearths should comply in size and construc-
tion so that it is in accordance with the provisions of the current Building Regulations Approved Document J.
The clearance distances to combustible material beneath, surrounding or upon the hearth and walls adjacent to the
hearth should comply with the guidance on the separation of combustible material given in Building Regulations
Approved Document J and also in these stove instructions.
If the stove is to be installed on a wooden floor, it must be covered with a non-combustible material at least 12mm
thick, in accordance with Building Regulations Approved Document J, to a distance of 30 cm in front of the stove and
15 cm to each side measuring from the door of the combustion chamber.
Combustion air supply
In order for the stove to perform efficiently and safely there should be an adequate air supply into the room in
which the stove is installed to provide combustion air. This is particularly necessary if the room is double-glazed or a
flue draught stabiliser is operating in the same room as the appliance. The provision of air supply to the stove must
be in accordance with current Building Regulations Approved Document J. An opening window is not appropriate
for this purpose. Air inlets must be positioned in such a way that they cannot be blocked. An air inlet may be a vent
(the vent must be open and the capacity of the vent sufficient when the stove is lit) or a fresh air system linked to
the stove.
The WESTFIRE UNIQ 35 are fitted as standard with a closed air supply collar, this enables the stove to take all
combustion air (primary, secondary and tertiary) directly from outside with 80mm pipe from the stove.
There are no European rules regarding the minimum distance to non-flammable walls, Westfire recommend leaving
a gap of at least 10 cm behind and to sides of stove.
FLUE AND AIR INTAKE POSITIONS
10


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Westfire WF35 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Westfire WF35 in the language / languages: English, German, Dutch, Danish, French as an attachment in your email.

The manual is 1.44 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info