10. Maintenance
The product does not require specific maintenance. It will suffice to check all connections once a year. Avoid moisture
and oil/soot/vapours, and keep the device clean.
11. Error Indications
With the procedures below, most errors can be quickly identified. If an error cannot be resolved, please refer to your
Victron Energy supplier.
11.1 General error indications
Problem
Cause
Solution
No output voltage on AC-out-2.
EasySolar-II GX in inverter mode
Unit will not switch over to generator or
mains operation.
Circuit breaker or fuse in the AC-in input
is open as a result of overload.
Remove overload or short circuit on AC-
out-1 or AC-out-2, and reset fuse/breaker.
Inverter operation not initiated when
switched on.
The battery voltage is excessively high or
too low. No voltage on DC connection.
Ensure that the battery voltage is within
the correct range.
'Low battery' The battery voltage is low.
Charge the battery or check the battery
connections.
'Low battery' (Shutdown)
The converter switches off because the
battery voltage is too low.
Charge the battery or check the battery
connections.
'Overload'
The converter load is higher than the
nominal load.
Reduce the load.
'Overload' (Shutdown)
The converter is switched off due to
excessively high load. Reduce the load.
'Over Temperature' The environmental temperature is high,
or the load is too high.
Install the converter in cool and well-
ventilated environment, or reduce the
load.
'Low Bat V Overload' (Shutdown) Low battery voltage and excessively high
load.
Charge the batteries, disconnect or
reduce the load, or install higher capacity
batteries. Fit shorter and/or thicker
battery cables.
'High DC Ripple' Ripple voltage on the DC connection
exceeds 1,5Vrms.
Check the battery cables and battery
connections. Check whether battery
capacity is sufficiently high, and increase
this if necessary.
'DC Ripple Shutdown'
The inverter is switched off due to an
excessively high ripple voltage on the
input.
Install batteries with a larger capacity. Fit
shorter and/or thicker battery cables, and
reset the inverter (switch off, and then on
again).
The charger does not operate. The AC input voltage or frequency is not
within the range set.
Ensure that the AC input is between
185VAC and 265VAC, and that the
frequency is within the range set (default
setting 45-65 Hz).
Circuit breaker or fuse in the AC-in input
is open as a result of overload.
Remove overload or short circuit on AC-
out-1 or AC-out-2, and reset fuse/breaker.
The battery fuse has blown.
Replace the battery fuse.
The distortion or the AC input voltage is
too large (generally generator supply).
Turn the settings WeakAC and dynamic
current limiter on.
The charger does not operate. 'Bulk
Protection' shown.
EasySolar-II GX is in 'Bulk protection'
mode thus, the maximum bulk charging
time of 10 hours is exceeded. Such a long
charging time could indicate a system
error (e.g. a battery cell short-circuit).
Check your batteries. NOTE: You can reset
the error mode by switching off and back
on the EasySolar-II GX. The standard
EasySolar-II GX factory setting of the 'Bulk
protection' mode is switched on. The
'Bulk protection' mode can be switched
off with help of VEConfigure only.
The battery is not completely charged. Charging current excessively high,
causing premature absorption phase.
Set the charging current to a level
between 0.1 and 0.2 times the battery
capacity.
Poor battery connection.
Check the battery connections.
The absorption voltage has been set to
an incorrect level (too low).
Set the absorption voltage to the correct
level.
The float voltage has been set to an
incorrect level (too low).
Set the float voltage to the correct level.
The available charging time is too short
to fully charge the battery.
Select a longer charging time or higher
charging current.
The absorption time is too short. For
adaptive charging this can be caused by
Reduce the charging current or select the
'fixed' charging characteristics.
17


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Victron EasySolar-II 48 3000 35-32 MPPT 250 70 GX at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Victron EasySolar-II 48 3000 35-32 MPPT 250 70 GX in the language / languages: English, German, Dutch, French, Italian, Swedish, Spanish as an attachment in your email.

The manual is 2.84 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info