Room temperature controller RAM 713 S
theben
Version: Sep-12 (subject to change) Seite 20 von 56
3.4.4 Actual value
Table 13
Designation
Values
Meaning
Use which actual value
From internal sensor
Fixed setting if E3 is not used
for an external sensor.
An external sensor can be
selected via the “Function of
E3” parameter on the settings
parameter page.
Function of the external
sensor
Temperature control sensor
(flush-mounted housing)
Floor sensor for temperature
control
Floor sensor for temperature
control
This parameter is only visible
if E3 is configured as a
temperature sensor input.
The room temperature is
measured using the external
sensor. The internal sensor is
deactivated.
The room temperature is
measured using the internal
sensor. The external sensor
monitors the underfloor
temperature.
(see below: Minimum and
maximum floor temperature).
Only the floor temperature is
measured and used as the
basis for temperature control.
Minimum floor temperature
No lower limit
10°C, 12°C, 14°C
16°C, 18°C, 20 °C
22°C, 24°C, 26°C
28°C, 30°C
The floor temperature is
controlled by RAM 713 S
depending on the room
temperature. However, the
floor temperature is not
exceeded even when the
setpoint temperature has
reached the set minimum
value.*
This setting prevents “cold
feet.”
* Exception: If the setpoint value is exceeded in the heating and cooling operating mode it
switches to cooling and stops sending the heating control variable.
20


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Theben RAMSES 713 S KNX at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Theben RAMSES 713 S KNX in the language / languages: English as an attachment in your email.

The manual is 0,4 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Theben RAMSES 713 S KNX

Theben RAMSES 713 S KNX User Manual - English - 1 pages

Theben RAMSES 713 S KNX User Manual - German - 56 pages

Theben RAMSES 713 S KNX User Manual - German - 1 pages

Theben RAMSES 713 S KNX User Manual - Dutch - 57 pages

Theben RAMSES 713 S KNX User Manual - Dutch - 1 pages

Theben RAMSES 713 S KNX User Manual - French - 59 pages

Theben RAMSES 713 S KNX User Manual - French - 1 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info