6.6 Temperature control
6.6.1 Introduction
If the RAM 712 is not configured as a switching controller, it can alternatively be configured as a
P or as a PI controller, whereby PI control is preferable.
With the proportional control (P control), the control variable is statically adjusted to the control
deviation.
The proportional integral control (PI control) is far more flexible, i.e. controls more quickly and
more accurately.
To explain the function of both temperature controls, the following example compares the room
to be heated with a vessel.
The filling level of the vessel denotes the room temperature.
The water supply denotes the radiator output.
The heat loss from the room is illustrated by a curve.
In our example, the maximum supply volume is 4 litres per minute and also denotes the
maximum radiator output.
This maximum output is achieved with an actuating value of 100%.
Accordingly, with an actuating value of 50%, only half the water volume, i.e. 2 litres per minute,
would flow into our vessel.
The bandwidth is 4l.
This means that the controller operates at 100% provided the actual value is smaller than, or
equal, to (211 – 41) = 171.
Function:
Desired filling volume:
21 litres (= setpoint)
From what point should the supply flow gradually be reduced to avoid an overflow? :
4l below the desired filling volume, i.e. at 21l – 41 = 171 (=bandwidth)
Original filling volume
15l (=actual value)
The loss amounts to 1l/minute
59


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Theben RAMSES 712 KNX at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Theben RAMSES 712 KNX in the language / languages: English as an attachment in your email.

The manual is 0,55 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Theben RAMSES 712 KNX

Theben RAMSES 712 KNX User Manual - English - 2 pages

Theben RAMSES 712 KNX User Manual - German - 67 pages

Theben RAMSES 712 KNX User Manual - German - 2 pages

Theben RAMSES 712 KNX User Manual - Dutch - 2 pages

Theben RAMSES 712 KNX User Manual - Dutch - 61 pages

Theben RAMSES 712 KNX User Manual - French - 62 pages

Theben RAMSES 712 KNX User Manual - French - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info