The diagram shows the influence of the selected characteristic curve steepness
(standard curve) on the calculated reference flow
temperature of the heating unit. The correct characteristic curve is determined
by defining the intersection point of the maximal calculated flow temperature
(=design temperature) at minimal outdoor temperature.
Example: The design temperature of the heater 60 °C flow at lowest outdoor
temperature according to calculation of heat requirement
-12 °C. The intersection point renders a slope of 1.2 as the setting.
Day Correction
Parallel characteristic translation
The day correction causes a parallel shift of the heating curve during daytime operating hours, because with certain outdoor tem-
peratures the building might not be optimally heated with the set heating curve. With a non-optimised heating curve, the following situ-
ations frequently occur: hot weather = room too cold/cold weather = room too hot. In this case, the slope of the curve should be reduced
stepwise by 0.2 points and increases the day correction
by 2 ... 4 °C each.
Night Correction
Parallel characteristic translation
The night correction produces a parallel translation of the heating characteristic during the nighttime operating hours. If a negative value
is set for the night correction, the reference flow temperature is lowered accordingly during the nighttime operating hours. In this manner,
primarily at night, but also during the day when no-one is at home, the room temperature is lowered, thus saving energy. Example: A
day correction of +5 °C and a night correction of -2 °C produces a reference flow temperature in nighttime operation that is 7 °C lower.
Comfort Temperature Boost
Parallel characteristic translation
The comfort temperature boost is added to the set day correction. In this manner it is possible to carry out quick heating and/or raise the
temperature of living spaces at a certain time each day.
Min. Flow
The minimum flow temperature is the lower limit of the heating curve, and by this, the reference flow temperature of the heating circuit. In
addition to that, the minimal flow temperature is the reference flow temperature for the frost protection function.
Max. Flow
This value is the upper limit of the reference flow temperature of the heating circuit If however, the temperature of the heating circuit
exceeds the set value, the heat circuit shuts down until the temperature falls below this value. After 55 seconds, rinse for 5 seconds.
The customer must provide an additional limiting thermostat which is connected to the pumps in series (eg underfloor heat-
ing) for safety.
Heating circuit off
If you use a room controller, the heating circuit can also be switched off on the base of the room controller in addition to the switch-off
according to outside temperature.
Summer: Heating circuit turns off when the summer/winter time changeover (outside temperature) is exceeded.
Summer + Room: Heating circuit is turned off as soon as the summer/winter time changeover (outside temperature) or the room set-
point temperatures are exceeded.
20
20


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Sorel MHCC 24V at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Sorel MHCC 24V in the language / languages: English as an attachment in your email.

The manual is 2 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Sorel MHCC 24V

Sorel MHCC 24V User Manual - German - 30 pages

Sorel MHCC 24V User Manual - French - 28 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info