The closing process is automatically initiated after
the open holding and clearing time.
Door closes.
Door CLOSE end position.
INFORMATION
If several vehicles are driving in the garage,
the induction loop and thereby the open
holding time are restarted every time it is
triggered.
11.9 ALARM and SAFETY connection
ALARM
A potential-neutral NC contact can be connected to this
terminal, for example a fire alarm system.
ALARM
A
FETY
AFETY
Fig. ALARM access
The status LED for the ALARM lights up green when the
contact is closed.
If the ALARM safety input is open, the command for door
OPEN is triggered:
Operator starts from door CLOSE end position,
drives to door OPEN end position and stays there.
Green trafc light for the interior and red trafc light
for the exterior start to ash quickly.
Commands are now ignored.
NOTE
The door system and the operator must
be checked before resetting the ALARM
safety input. All damages must be repaired
without delay.
CLOCK OUT for exterior request side
CLOCK
IN
OU
T
CL
IN
Fig. Timer connection (CLOCK OUT)
This connection is selected to keep the door open for a
certain amount of time in the evening hours. Vehicles can
enter the garage from the exterior.
Status LED lights up orange during the activation.
With the rst command, the door opens to the door
OPEN end position.
Exterior request side now receives drive
authorisation:
Interior: Exterior red phase: Green phase.
The door remains open until the CLOCK OUT
contact is activated.
After the desired time, the contact at the CLOCK
OUT connection drops out.
The closing process is automatically initiated after
the open holding and clearing time.
Door closes.
Door CLOSE end position.
INDUCTOR
A potential-neutral NO contact from an evaluation unit of
an induction loop can be connected to this terminal.
INDUCTOR
Fig. INDUCTOR connection
The status LED for the INDUCTOR lights up orange
when the contact is activated.
If the contact is activated, a command from the interior
is triggered. When driving through the induction loop, a
command is sent to the control unit:
Operator opens the door to the door OPEN end
position.
Interior request side now receives drive
authorisation.
Interior: Green phase.
Exterior: Red phase.
11. Connections and special functions of the
wall control unit
69


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Sommer S 9060 Tiga plus at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Sommer S 9060 Tiga plus in the language / languages: English as an attachment in your email.

The manual is 10,99 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Sommer S 9060 Tiga plus

Sommer S 9060 Tiga plus User Manual - German - 100 pages

Sommer S 9060 Tiga plus User Manual - Dutch - 100 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info