555849
6
Zoom out
Zoom in
Previous page
1/8
Next page
CE2N2462E / 09.12.1998 Siemens Building Technologies
6/8 Landis & Staefa Division
When connecting an external switching contact to the controller's terminals A6-MD, the
operating mode can be selected from a remote location:
Contact closed: controller is in standby mode
Contact open: controller uses the operating mode selected with the slider
The wires of the measuring circuits carry extra low voltage
The wires to the actuator and the pump carry AC 24...230 V
The local electrical regulations must be complied with
Detector cables must not be run parallel to mains carrying cable for loads such as
actuator, pump, burner, etc. (safety class II to EN 60730)
The maximum limitation of the boiler temperature may not be used as a safety function.
For that purpose a thermostat or safety limiter must be connected at terminals L-F1/F4
Setpoint adjustments:
Normal temperature (in °C room temperature)
Setback (in °C room temperature)
D.h.w. (only with the RVP210)
Settings to be made by the heating engineer:
Slope of heating curve
Authority of room temperature
ECO heating limit
Maximum limitation of the flow or boiler temperature
Type of regulating unit (mixing valve or burner)
Type of control (three- or two-position)
Frost protection activated or deactivated
Priority of d.h.w. heating (only with the RVP210)
The controller is supplied complete with installation instructions and operating instruc-
tions.
- conformance to
EMC directive 89/336/ EEC
Immunity EN 50082-2
Emissions EN 50081-1
Low voltage directive 73/23/ EEC
Safety EN 60730-1
Rated operating voltage AC 230 V ±10 %
Frequency 50 Hz
Power consumption 7 VA
Degree of protection (cover closed) IP40 D EN 60529
Safety class II EN 60730
Permissible ambient temperatures
Transport 25...+70 °C
Storage 5...+55 °C
Operation 0...50 °C
Weight (net) 0.72 kg
Test class II
Rated voltage AC 230 V
Rated current 2 (2) A
Contact current at AC 24...90 V 0.1...2 A, cos ϕ >0.5
Contact current at AC 90...250 V 0.02...2 A, cos ϕ >0.5
Rated current of ignition transformer 1 A max.(30 s max.)
Switch-on current of ignition transformer 10 A max.(10 ms max.)
Setpoint of normal room temperature 20 ±0...8 °C
Setback for reduced room temperature 12...0 K
Setpoint of d.h.w. temperature (only with the RVP210) 10...60 °C
Slope of heating curve 0.25...4
Max. limit of flow or boiler temperature 8...100 °C
ECO heating limit 10...+8 °C (referred to normal setpoint)
Authority of room temperature 0...100 %
Switching differential with two-position control 1...20 K
Analog time switches 12 hours
Digital weekly time switch with backup battery
Switching contact
Notes
Engineering
Commissioning
Technical data
General data
Output relays
Setting ranges
Backup of time switches
6


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RVP210 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RVP210 in the language / languages: English as an attachment in your email.

The manual is 0,76 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info