555849
3
Zoom out
Zoom in
Previous page
1/8
Next page
Siemens Building Technologies CE2N2462E / 09.12.1998
Landis & Staefa Division 3/8
All electric or electro-hydraulic actuators for three-position control made by Landis &
Staefa can be used:
Operating voltage AC 24...230 V
Maximum running time 6 minutes (recommended: 2 to 3 minutes)
All electro-thermal actuators for two-position control:
Operating voltage AC 24...230 V
Running time 8 to 16 minutes
When ordering, please give type reference according to "Type summary". If a controller
with a weekly time switch is required, it must be ordered without the time switch, that is,
RVP200.0
or
RVP210.0
, plus the required time switch (
AUZ3.7
or
AUD3
). Detectors,
room unit, actuator and valve must be ordered as separate items.
Weather-compensated control: the setpoint of the flow or boiler temperature is con-
tinuously shifted in function of the outside temperature (via the outside detector). As-
signment of the flow temperature to the actual outside temperature is made via the
heating curve. Its slope is adjustable
Weather-compensated control with room temperature influence: the setpoint of the
flow or boiler temperature is continuously shifted in function of the outside tempera-
ture (via the outside detector) and, in addition, in function of the setpoint / actual value
deviation of the room temperature.
Room temperature authority = 199 % (adjustable, guide value is 50 %)
Room temperature-compensated control: the setpoint of the flow or boiler tempera-
ture is continuously shifted in function of the setpoint / actual value deviation of the
room temperature
With both types of weather-compensated control, the composite outside temperature is
used as the compensating variable. It is generated from the actual and the attenuated
outside temperature. Compared to the actual outside temperature it is ssignificantly at-
tenuated and delayed.
20 10
0
-10 -20 -30
90
80
70
60
50
40
30
4
3,5 3 2,75 2,5 2,25
2
1,75
1,5
1,25
1
0,75
0,5
0,25
100
2462D01
T
V
T
A
110
20
T
A
Outside temperature [°C]
T
V
Flow temperature[°C]
Three-position control: the flow temperature is controlled continuously with no offset
via a seat or slipper valve driven by an electric or electro-hydraulic actuator
Two-position control: the flow temperature is controlled via a seat or slipper valve
driven by an electro-thermal actuator. The switching differential is 1 K
Maximum limitation of the flow temperature can be provided in the range 8100 °C.
This function can be deactivated.
The boiler temperature is controlled by a single-stage burner which is switched on and
off. The burner's minimum on time is four minutes. The switching differential is adjust-
able in the range 120 K.
Maximum limitation of the boiler temperature can be provided in the range 8100 °C.
This function can be deactivated.
If the boiler temperature falls below 5 °C, the burner will be switched on to maintain a
minimum boiler temperature.
When there is no demand for heat and during quick setback, the boiler will be switched off.
Suitable actuators
Ordering
Technical design
Compensating variables
Heating curve chart
Flow temperature control
Boiler temperature control
3


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RVP210 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RVP210 in the language / languages: English as an attachment in your email.

The manual is 0,76 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info