Siemens Heating controllers RVP201 and RVP211 CE1P2464en
Building Technologies 3 Technical design 12.12.2007
3.6 Frost protection for the plant and the building
3.6.1 Frost protection for the plant
Frost protection for the plant provides protection against freezing by activating the heat-
ing circuit pump, if controller and heat generating equipment are ready to operate
(mains voltage present).
Frost protection for the plant can be provided with or without an outside sensor. The
switching differential is 1 K (fixed value).
Frost protection is always active, even if the control is switched off (operating modes
and
), with quick setback, and with Off through ECO.
If desired, frost protection for the plant can be deactivated with the coding switch “Frost
protection”.
Frost protection for the plant is accomplished in two steps:
1. If the outside temperature falls to 1.5 °C, the heating circuit pump will be activated
for 10 minutes at 6-hour intervals.
2. If the outside temperature falls to –5 °C, the heating circuit pump will be activated
and runs continuously.
The frost protection stage active at a time will be switched off when the outside tempera-
ture has exceeded the limit value by an amount equal to the switching differential of 1 K.
Frost protection for the plant is accomplished in two steps:
1.
If the flow temperature falls to 10 °C, the heating circuit pump will be actuated
for 10 minutes at 6-hour intervals.
2.
If the flow temperature falls to 5 °C, the heating circuit pump will be actuated
and runs continuously.
The frost protection stage active at a time will be switched off when the flow temperature
has exceeded the limit value by an amount equal to the switching differential of 1 K.
3.6.2 Frost protection for the building
Frost protection for the building protects the rooms from excessively low temperatures.
It acts in all operating modes as a minimum limitation of the room temperature. It can
be achieved with or without room unit, provided the heating curve slope is correctly set.
The frost protection for the building is given higher priority over the ECO automatic
energy saver. If desired, frost protection for the building can be deactivated with the
coding switch “Frost protection”.
Without room unit:
Attenuated outside temperature 5 °C: the control is switched on and the flow
temperature is controlled such that a room temperature of 5 °C will be maintained
Attenuated outside temperature >6 °C: the control is switched off
With room unit and with quick setback active:
Room temperature 5 °C: the control is switched on and the flow temperature is
controlled such that a room temperature of 5 °C will be maintained
Room temperature >6 °C: the control is switched off
With room unit, but without quick setback:
Same as without room unit
With outside sensor
Without outside sensor
24


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RVP201 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RVP201 in the language / languages: English as an attachment in your email.

The manual is 0,75 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RVP201

Siemens RVP201 Installation Guide - English, German, Dutch, Danish, French, Italian, Swedish, Spanish, Finnish - 26 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info