Siemens Heating controllers RVP201 and RVP211 CE1P2464en
Building Technologies 3 Technical design 12.12.2007
3.7 D.h.w. heating
3.7.1 General
Only the RVP211 provides d.h.w. heating. It supports operation with the charging pump
or the changeover valve.
For d.h.w. heating, the RVP211 features:
a fourth output relay (Q3) for the control of the d.h.w. charging pump or the d.h.w.
changeover valve
a setting facility for the d.h.w. temperature setpoint
a setting facility for the priority
3.7.2 Acquisition of d.h.w. temperature
Refer to "3.2 Acquisition of actual values".
The d.h.w. temperature can also be acquired with a thermostat, at the expense of re-
duced functionality, however.
Since all measuring circuits use low voltage, an intermediate relay is required. The
thermostat controls the relay whose contacts are connected to terminals B3-M (also
refer to "5.2 Connection diagrams").
On the thermostat, the setpoint of the d.h.w. temperature is set. If the d.h.w. tempera-
ture falls below the setpoint, the thermostat will energize the relay, and the controller
interprets the bridging of terminals B3-M as a demand for d.h.w. heating.
Alternative to the relay: if a new thermostat is used, or a thermostat with new contacts,
the intermediate relay will not be required.
The contacts of the thermostat must meet the following requirements, however:
Transfer resistance <80
Voltage <10 V
Current 10 mA
The contacts must be capable of switching reliably the required voltage and current.
3.7.3 D.h.w. heating with charging pump
D.h.w. heating with a charging pump can be employed either with mixing valve opera-
tion (flow temperature control) or boiler operation (boiler temperature control).
To ensure fast d.h.w. heating, the other heating loads can be restricted during the time
the d.h.w. is heated (priority). The following choices are available:
Absolute priority:
During d.h.w. heating, the heating circuit pump is locked, which means that all other
heating loads will be dead.
In the case of underfloor or ceiling heating systems, as well as boiler operation, ab-
solute priority is mandatory
No priority (parallel operation):
Both heating circuit pump and charging pump operate at the same time
If the sensor acquires a d.h.w. temperature that lies 5 K below the d.h.w. temperature
setpoint (or if the contact of the d.h.w. thermostat closes), the charging pump will be
activated. During d.h.w. heating, the flow temperature is raised to a level that is 16 K
(fixed value) higher than the adjusted setpoint of the d.h.w. temperature.
When the d.h.w. temperature reaches the setpoint, the charging pump will be deacti-
vated again. If the d.h.w. temperature falls to a level that lies 5 K below the setpoint
(switching differential), the charging pump will be activated again.
Enabling of d.h.w. heating:
Measurement with
a sensor
Measurement with
a thermostat
Priority
Heating
25


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RVP201 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RVP201 in the language / languages: English as an attachment in your email.

The manual is 0,75 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RVP201

Siemens RVP201 Installation Guide - English, German, Dutch, Danish, French, Italian, Swedish, Spanish, Finnish - 26 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info