Siemens Heating controllers RVP201 and RVP211 CE1P2464en
Building Technologies 3 Technical design 12.12.2007
3.2.5 D.h.w. temperature
The d.h.w. temperature can be acquired with either a sensor or thermostat. For details
on the use of a thermostat, refer to "3.7 D.h.w. heating".
Suitable are all temperature sensors with a sensing element LG-Ni 1000 at 0 °C:
Immersion temperature sensor QAE212…
Immersion temperature sensor QAP21.3 (complete with a ready connected cable)
It is not possible to configure whether a sensor or a thermostat is connected. For this
reason, a short-circuit or interruption are permitted statuses so that no fault message
can be generated.
3.3 Flow or boiler temperature control
3.3.1 Setpoint adjustments
The following manual adjustments are made on the controller:
Setpoint for the normal temperature. The mid-position of the setting knob's scale
corresponds to a setpoint of 20 °C. Readjustments can be made within a range of ±
8 °C, giving a total setting range of 12…28 °C.
Setback for the reduced temperature. The setting knob's scale represents the set-
point for the normal temperature. The setback is adjustable within a range of
0…–12 °C.
The setpoints of the normal and the reduced temperature are entered directly in °C
room temperature. They are independent of whether or not the control uses a room
temperature sensor.
The lowest valid room temperature setpoint always represents the minimum setpoint for
the frost protection for the plant, even if a lower value has been set as the setpoint for
the reduced temperature. The setpoint for the frost protection for the plant is 5 °C (fixed
value).
3.3.2 Heating program
The controller has a plug-in type time switch for entering a 24-hour or weekly heating
program. For each heating period that uses the normal temperature, the start and end
of the period need to be set. Outside of the selected heating periods, the reduced tem-
perature
or protection temperature will be maintained.
With each type of time switch, several heating phases per day can be set.
In the automatic modes without using a time switch, the lower temperature (reduced or
frost protection) will be maintained.
The room unit QAW70 is used to override the heating program. For details, also refer to
"6 Mechanical design".
3.3.3 Compensating variables
The RVP201/211 differentiates between three types of outside temperatures:
The actual outside temperature (T
A
)
The attenuated outside temperature (T
AD
). It is generated by filtering the actual out-
side temperature by the building time constant. This means that compared to the ac-
tual outside temperature, the attenuated outside temperature is significantly damp-
ened, thereby representing the long-term development of the outside temperature.
The building time constant is a measure of the type of building structure and indi-
Types of sensors
Handling of faults
Outside temperature
14


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RVP201 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RVP201 in the language / languages: English as an attachment in your email.

The manual is 0,75 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RVP201

Siemens RVP201 Installation Guide - English, German, Dutch, Danish, French, Italian, Swedish, Spanish, Finnish - 26 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info