Siemens Heating controllers RVP201 and RVP211 CE1P2464en
Building Technologies 3 Technical design 12.12.2007
0 %, Off = room temperature deviation has no impact on the setpoint generation
100 % = maximum impact of room temperature deviation on the setpoint generation
This function requires a room temperature sensor (room unit).
2462D05
w
R
- x
R
E
Gain factor of room temperature deviation
w
R
Decrease of room temperature setpoint
+w
R
Increase of room temperature setpoint
E Authority
w
R
-x
R
Setpoint minus actual value (room temperature)
The change w
R
of the room temperature setpoint is calculated in a static state using
the following formula:
Gain factor
[%]
w
R
=
––––––––––––––––
× ( w
R
-x
R
)
10
2462D06
s
Impact of change of room temperature setpoint on the flow tempera-
ture setpoint
w
R
Change of room temperature setpoint
s Slope of heating curve
w
VT
Change of flow temperature setpoint
The change w
VT
of the flow temperature setpoint is calculated using the following
formula:
w
VT
= w
R
× ( s + 1 )
3.3.4 Heating curve chart
With weather-compensated flow temperature control (with or without room temperature
influence), the heating curve assigns the flow temperature setpoint to the prevailing
outside temperature. The heating curve slope is set with a setting knob on the front of
the controller.
General, basic setting
16


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RVP201 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RVP201 in the language / languages: English as an attachment in your email.

The manual is 0,75 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RVP201

Siemens RVP201 Installation Guide - English, German, Dutch, Danish, French, Italian, Swedish, Spanish, Finnish - 26 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info